18
TT-1625 7/17
Use solid or stranded 14-22 gauge wire. To determine
the wire gauge, measure the cable distance between
the controller and master RSA III.
For example, if the cable distance between the
controller and the master RSA III is 122 m (400 ft.), then
the total wire length for each conductor is 122 m
(400 ft.). According to the chart in Figure 19, this
example requires 22-gauge wire.
Throughout step 6, refer to the following illustrations.
See Figure 20 for RSA III circuit board connectors. See
Figure 41 for RSA III circuit board terminal connections.
See Figure 57 to Figure 63 for the RSA III wiring
diagrams and Figure 64 and Figure 65 for the
RSA III interconnection diagrams.
GM86125-
1. P39, 3-pin Isolated/non-isolated jumper
2. P27, 6-pin RS-485 connections
3. P34, 3-pin RS-485 termination resistor for last device
4. P41, 8-pin Input (EPS/User) connections
1
2
3
Top View
Bottom View
4
5
6
7
5. P42, 4-pin Input user 4 & 5 connections
6. P40, 6-pin Common fault and horn dry contacts
7. P37, 3-pin Power/CAN connections
Figure 20
RSA III Circuit Board GM86125 Connectors
The RSA III has the following wiring and selections:
D
P27, 6-pin RS-485 connections (communication
between controller and RSA III master).
See
step 6.3.
D
P27, 6-pin RS-485 connections (communication
between RSA III master and RSA III slaves). See
step 6.4.
D
P34, 3-pin RS-485 termination resistor for last
device. See step 6.4.
D
P37, 3-pin power/CAN connections. See step 6.5.
D
P39, 3-pin isolated/non-isolated jumper.
See
step 6.6.
D
P40, 6-pin common fault and horn dry contacts. See
step 6.7.
D
P41, 8-pin input (EPS/user) connections.
See
step 6.8.
D
P42, 4-pin input user 4 & 5 connections. See
step 6.11.
6.1
Deenergize the 12/24-volt DC power source to
each RSA III, if not already done.
6.2
Flush mount RSA III only.
When using a
flush-mount RSA III box with a bushing, it is
recommended to run all wiring to the RSA III box
and then mount it to the wall or to the electrical
box in the wall. Check that box is square to the
wall; adjust as needed. After the RSA III box is
mounted,
make
the
individual
electrical
connections to the RSA III circuit board as
described in the following steps.
Position wall-mounting plate GM85126 against
the RSA III bezel GM85134
prior
to attaching the
wiring.
Summary of Contents for APM802
Page 14: ...14 TT 1625 7 17 Figure 15 Remote Serial Annunciator Dimension Print ADV 8661A...
Page 15: ...TT 1625 7 17 15 Figure 16 Remote Serial Annunciator Dimension Print ADV 8661B modified...
Page 31: ...TT 1625 7 17 31 Figure 53 RSA III Generator Set and ATS Setup on SiteTecht Sample Screen...
Page 36: ...36 TT 1625 7 17 Figure 57 RSA III Wiring Diagram GM62554A J...
Page 37: ...TT 1625 7 17 37 Figure 58 RSA III Wiring Diagram GM62554B J...
Page 38: ...38 TT 1625 7 17 Figure 59 RSA III Wiring Diagram GM62554C J...
Page 39: ...TT 1625 7 17 39 Figure 60 RSA III Wiring Diagram GM62554D J...
Page 40: ...40 TT 1625 7 17 Figure 61 RSA III Wiring Diagram GM62554E J...
Page 41: ...TT 1625 7 17 41 Figure 62 RSA III Wiring Diagram GM62554F J...
Page 42: ...42 TT 1625 7 17 Figure 63 RSA III Wiring Diagram GM62554G J...
Page 43: ...TT 1625 7 17 43 Figure 64 RSA III Interconnection Diagram ADV 6990A H...
Page 44: ...44 TT 1625 7 17 Figure 65 RSA III Interconnection Diagram ADV 6990B H...
Page 46: ...46 TT 1625 7 17 Notes...
Page 47: ...TT 1625 7 17 47 Notes...