12
TT-1625 7/17
3.
Mount the communication module board
in the DEC 3+ controller.
Note:
Requires DEC 3+ controller logic (red) circuit
board GM28725.
Note:
Perform step 3 with GM91356-S4, -S5, or -S6
and GM32644-KP1 kit.
3.1
Remove the existing three nuts attaching the
indicator panel circuit board. Leave the existing
washers in place. The nuts will be reused.
3.2
Attach the three spacers to the indicator panel
circuit board studs. See Figure 10.
3.3
Position
communication
module
board
GM49791-1 on the spacers.
Note:
If procedure requires installing a communication
module board, refer to TT-1285 Program Loader
Software instructions for downloading firmware
version
1.23 or higher with red controller
board or 2.03 or higher with blue controller
board.
The download should be performed in
step 8. Configure the DEC 3+ controller for the
remote serial annunciator.
3.4
Install three lock washers (X-22-7) from the kit or
from step 2.3 and the existing three nuts on the
spacers to secure the communication module
board. Do not overtighten the nuts.
4.
Wire the communication module board
in the DEC 3+ controller.
4.1
Attach the 24-position ribbon cable GM32632
inline connector to the communication module
board P9 connector. The connector is polarized
and mates in one position only.
4.2
Attach the 10-position ribbon cable GM21340 to
the communication module board P8 connector
and the main circuit board P7 connector. The
connectors are polarized and mate in one
position only.
GM32644-B
1. Ribbon cable, 10 position GM21340
2. DEC 3+ controller main circuit board
3. Ribbon cable, 24 position GM32632
4. Existing nuts (3)
5. Lock washers (3), X-22-7
6. Spacers (3) GM32633
7. Existing washers (3)
8. Existing indicator panel circuit board
9. Communication module board GM49791-1
2
1
4
5
6
7
8
9
3
Figure 10
Mounting Communication Module Board in
the DEC 3+ Controller
4.3
If the unit previously had the GM49791-2 gauge
drive circuit board installed, reconnect cable P10
to the communication module board.
4.4
High Battery Voltage.
Locate T27 lead on the
indicator
panel
assembly
and
connect
communication board HBV harness GM35318.
Use the terminal connector on GM35318 with the
two leads together. Verify that the stripped end of
the
harness
is
securely
connected
to
communication module board terminal TB5-12.
See Figure 9 for an illustration of the wiring
connection. See Figure 11 and Figure 12 for the
communication module board terminal strip
location and terminal designations.
GM32644-F
Figure 11
Communication Module Board
Summary of Contents for APM802
Page 14: ...14 TT 1625 7 17 Figure 15 Remote Serial Annunciator Dimension Print ADV 8661A...
Page 15: ...TT 1625 7 17 15 Figure 16 Remote Serial Annunciator Dimension Print ADV 8661B modified...
Page 31: ...TT 1625 7 17 31 Figure 53 RSA III Generator Set and ATS Setup on SiteTecht Sample Screen...
Page 36: ...36 TT 1625 7 17 Figure 57 RSA III Wiring Diagram GM62554A J...
Page 37: ...TT 1625 7 17 37 Figure 58 RSA III Wiring Diagram GM62554B J...
Page 38: ...38 TT 1625 7 17 Figure 59 RSA III Wiring Diagram GM62554C J...
Page 39: ...TT 1625 7 17 39 Figure 60 RSA III Wiring Diagram GM62554D J...
Page 40: ...40 TT 1625 7 17 Figure 61 RSA III Wiring Diagram GM62554E J...
Page 41: ...TT 1625 7 17 41 Figure 62 RSA III Wiring Diagram GM62554F J...
Page 42: ...42 TT 1625 7 17 Figure 63 RSA III Wiring Diagram GM62554G J...
Page 43: ...TT 1625 7 17 43 Figure 64 RSA III Interconnection Diagram ADV 6990A H...
Page 44: ...44 TT 1625 7 17 Figure 65 RSA III Interconnection Diagram ADV 6990B H...
Page 46: ...46 TT 1625 7 17 Notes...
Page 47: ...TT 1625 7 17 47 Notes...