34
TT-1625 7/17
Identity
The identity field provides the user read only information
including the
Firmware (Software) Version
. Record
this
number
for
upgrading
firmware
when
troubleshooting.
Modbus
r
The
Modbus
r
Baud Rate
is selectable and must be the
same for all connected devices. The Modbus
r
field
establishes the RSA III as a master or slave. Enter true
or false to the
Is Modbus Master?
line item. When used
as a slave, create a
Modbus
r
Slave Address
to
identify this RSA III on the Modbus
r
network.
The
Modbus
r
Timeout Factor
is a user-selectable
entry of 1 (fast)--10 (slow) with the default setting of 5.
Typically the default setting will provide adequate
system performance. The user may increase/decrease
the timeout factor as needed to optimize the RSA III with
the network system.
Line items
Received Modbus
r
Message Count
and
Modbus
r
Error Count
indicate the performance of the
network. Showing Modbus
r
Error Count instances is
typical of some network communications and not a
reason for concern.
Product Connections
The generator set and ATS product IDs are no longer
user configurable. The IDs are recognized by the
RSA III at the specified Modbus address.
See
Figure 53.
The product connection field requires three entries
(Product, Address, and Timeout).
The device description or
Product
identifies what type
of device is connected to the RSA III master such as a
generator set, transfer switch (ATS), or RSA III slave(s).
Each connection requires a unique
Address
. Change
the default setting as needed to create different
addresses based on the range of 1--247. In addition,
each field creates addresses for each of the RSA III
slaves. Up to five slaves can be driven by one RSA III
master.
The Modbus
r
Timeout
period is separately assignable
for each device. The timeout period is a user-selectable
entry of 1--120 seconds with the default setting of
15 seconds. Increase the timeout factor as needed
when working with a slow or unstable network to prevent
interruption or nuisance timeouts.
The
Connected ATS
parameter indicates if the RSA III
should expect an ATS on the network at the address
specified. When set to True, the RSA III notifies the user
when it cannot communicate with the ATS. If the RSA III
auto-detection logic finds an ATS on the network, the
RSA III sets the ATS connected parameter to True and
saves the setting. Should the ATS be removed from the
network for some reason, set this parameter back to
False.
Product Connection Inputs
The product connection input field provides the user
with choices to show selected status, warning, or
shutdown faults. EPS supplying load and three digital
inputs are available for monitoring.
For
EPS Supplying Load Indicator
connections, refer
to Figure 56 to select the EPS source.
The
Source
can be from the generator set, ATS, or
(local) hardwired directly to the RSA III. Refer to
Figure 56.
Select the
Event Level
as either a warning (yellow light)
or fault shutdown (red light).
This field also provides an
Events Log
which is a history
of faults that the RSA III encounters while energized.
The generator set may or may not be running at the time
of the event. Review the Events Log for a summary of
the performance of the network communication.
Modbus
r
is a registered trademark of Schneider Electric.
Summary of Contents for APM802
Page 14: ...14 TT 1625 7 17 Figure 15 Remote Serial Annunciator Dimension Print ADV 8661A...
Page 15: ...TT 1625 7 17 15 Figure 16 Remote Serial Annunciator Dimension Print ADV 8661B modified...
Page 31: ...TT 1625 7 17 31 Figure 53 RSA III Generator Set and ATS Setup on SiteTecht Sample Screen...
Page 36: ...36 TT 1625 7 17 Figure 57 RSA III Wiring Diagram GM62554A J...
Page 37: ...TT 1625 7 17 37 Figure 58 RSA III Wiring Diagram GM62554B J...
Page 38: ...38 TT 1625 7 17 Figure 59 RSA III Wiring Diagram GM62554C J...
Page 39: ...TT 1625 7 17 39 Figure 60 RSA III Wiring Diagram GM62554D J...
Page 40: ...40 TT 1625 7 17 Figure 61 RSA III Wiring Diagram GM62554E J...
Page 41: ...TT 1625 7 17 41 Figure 62 RSA III Wiring Diagram GM62554F J...
Page 42: ...42 TT 1625 7 17 Figure 63 RSA III Wiring Diagram GM62554G J...
Page 43: ...TT 1625 7 17 43 Figure 64 RSA III Interconnection Diagram ADV 6990A H...
Page 44: ...44 TT 1625 7 17 Figure 65 RSA III Interconnection Diagram ADV 6990B H...
Page 46: ...46 TT 1625 7 17 Notes...