TT-1625 7/17
29
8.
Configure the DEC 3+ controller for the
remote serial annunciator.
Note: After setting DIP switches to the generator
set application,
be sure to
power down
and then
power up
the controller; either disconnect the
battery and then reconnect the battery of the
generator set, use the prime power switch (if
equipped), or remove and then replace the F2
controller fuse.
The controller will NOT
acknowledge the DIP switch change until after
generator set controller is
powered up
.
8.1
Set the controller Modbus
r
address to #1 by
placing DIP switches 6, 7, and 8 to the open
position. See Figure 50.
6126
1. Push this side down to open circuit.
OPEN
1
2
3
1
4 5
6
7 8
Figure 50
DEC 3+ Controller DIP Switches
8.2
The DEC 3+ controller baud rate is fixed at
19200. No change is required.
8.3
If the RSA III is used with a DEC 3+ controller and
it required installing a communication module
board, refer to TT-1285 Program Loader
Software instructions for downloading
firmware
version 1.23 or higher with red controller
board or 2.03 or higher with blue controller
board.
8.4
Replace the controller cover and hardware.
9.
Restore the generator set to service.
9.1
Place the generator set master switch in the
OFF/RESET position (OFF mode on the
Decision-Maker
e
8000 or Out-of-Service mode
on the APM802 controller).
9.2
Reconnect the generator set engine starting
battery, negative (--) lead last.
9.3
Reconnect power to the battery charger, if
equipped.
9.4
Energize the RSA III(s).
9.5
Place the generator set in AUTO (select AUT
mode on the Decision--Maker
e
8000) for startup
by remote transfer switch or remote start/stop
switch.
9.6
Reset alarm horns as needed.
10. Configure the APM802 controllers for the
remote serial annunciator.
The APM802 is factory configured to work with the
RSA III. The APM802 controller
defaults
to a 19200
baud rate and to an address of #1. Refer to Figure 51 for
the default APM802 controller settings.
Note:
The RS-485 address on the APM802 must match
the address on the RSA III master.
Serial Link Settings
Setting Selection
Speed
19200 bauds
Stop bit
1
Parity
Without
Function
Modbus slave
Slave number
1 (must match address on the
RSA III master)
Figure 51
APM802 Configuration
Summary of Contents for APM802
Page 14: ...14 TT 1625 7 17 Figure 15 Remote Serial Annunciator Dimension Print ADV 8661A...
Page 15: ...TT 1625 7 17 15 Figure 16 Remote Serial Annunciator Dimension Print ADV 8661B modified...
Page 31: ...TT 1625 7 17 31 Figure 53 RSA III Generator Set and ATS Setup on SiteTecht Sample Screen...
Page 36: ...36 TT 1625 7 17 Figure 57 RSA III Wiring Diagram GM62554A J...
Page 37: ...TT 1625 7 17 37 Figure 58 RSA III Wiring Diagram GM62554B J...
Page 38: ...38 TT 1625 7 17 Figure 59 RSA III Wiring Diagram GM62554C J...
Page 39: ...TT 1625 7 17 39 Figure 60 RSA III Wiring Diagram GM62554D J...
Page 40: ...40 TT 1625 7 17 Figure 61 RSA III Wiring Diagram GM62554E J...
Page 41: ...TT 1625 7 17 41 Figure 62 RSA III Wiring Diagram GM62554F J...
Page 42: ...42 TT 1625 7 17 Figure 63 RSA III Wiring Diagram GM62554G J...
Page 43: ...TT 1625 7 17 43 Figure 64 RSA III Interconnection Diagram ADV 6990A H...
Page 44: ...44 TT 1625 7 17 Figure 65 RSA III Interconnection Diagram ADV 6990B H...
Page 46: ...46 TT 1625 7 17 Notes...
Page 47: ...TT 1625 7 17 47 Notes...