32
C35-FC
AO1
AO2
AO3
24V
GND
G
D-
D+
GND
GND
GND
RTD
RTD
BIN1
GND
24V
AC/DC
/+
/-
S1
D1
T
T1
M1
V1
E1
+
6A
V2
AO
O3
Analog outputs
[V, DC]
10
t [s]
Figure 14.3.3. Connection diagram
Figure 14.3.4. Analog outputs
for two stage heating
14.4. 2-pipe fan coil/radiator and floor heating
HOME > MENU > ADVANCED > PARAMETERS [1/4]
Application type:
2-pipe & fl oor heating
Control sequence:
Heating only
Cooling
or
heating
Fan motor type:
EC motor
1
speed
motor*
3
speed
motor*
*use only with KOER FC-RB fan coil driver
HOME > MENU > ADVANCED > IN / OUT [1/2]
Binary input:
Window
contact
Presence
sensor
RTD Sensor function:
Floor
sensor
Temperature sensor:
Internal
Max fl oor temp:
5-40
°C
D1
– C35-FC
M1
– ECM fan (DC 0-10 V)
V1
– Cooling or heating valve actuator (DC 0-10 V)
E1
– Current valve for electric heater (DC 0-10 V)
V2
– Floor Heating valve actuator for radiator (DC 0-10 V)
S1
– Switch for window or presence sensor contact
T1
– Floor sensor (PT1000)
T1
V2
V1
M1
Figure 14.4.1. Functional
diagram with 2-pipe fan coil
and fl oor heating
T1
V2
V1
Figure 14.4.2. Functional
diagram with radiator and
fl oor heating
AO1
AO2
AO3
24V
GND
GND
GND
GND
RTD
RTD
BIN1
GND
24V
AC/DC
/+
/-
S1
D1
T
T1
M1
V1
V2
6A
Figure 14.4.3. Connection
diagram
14.5. Chilled or heated ceiling
HOME > MENU > ADVANCED > PARAMETERS [1/4]
Application type:
Chilled or heated ceiling
Control sequence:
Cooling only
Heating
only
Cooling
or
heating
HOME > MENU > ADVANCED > IN/OUT [1/2]
Binary input
:
Dew point sensor
RTD Sensor function:
Changeover
sensor
Remote
sensor
Temperature sensor:
Internal
Remote
H1
V1
T1
T1
Figure 14.5.1. Functional
diagram