12.3. Parameters
12.3.1. Parameters [1 / 4]
Main Confi guration
Application Type
The Application Type defi nes confi guration of the controlled system. By selecting one of the options,
the functionality of the analog outputs is changed. The following applications are available:
•
Application type: 2-pipe system
•
Application type: 4-pipe system
•
Application type: 2-pipe and aux. heater
•
Application type: Chilled/heated ceiling
•
Application type: Chill Ceiling/heat fl oor
•
Application type: 2-stage chill/heat ceiling
To see more details about application diagrams, go to chapter
14. Applications and connection
diagrams.
Lock Home Screen:
To
activate a user password on
the
Home screen, press the
Lock Home Screen button so
that its status is
On.
Unlock Setpoint Buttons:
This function allows users to
change the setpoint when
the Home screen is locked. It
can only be activated if the
Lock Home Screen function is
On. Users will not be able to
change operating and working
mode or enter the
Menu.
NOTE:
It is recommended to use setpoint limits (see chapter 12.5.
Setpoint Limits) to ensure
rational energy consumption when Setpoint buttons are unlocked.
Show only Setpoint values:
Turn this function On if you only want to show Setpoints on the
Home screen. Measured values will not be visible for the end users. Measured values can be
seen in
Offset menu (see chapter 12.4. Offset).
Return To Home screen:
When this function is enabled, the device will return to the
Home
screen automatically from any menu screen after 1 minute of inactivity.