30
C35-FC
13.3. Temperature Sensor
Users can defi ne how temperature readings will be measured by pressing the button next to
Temperature Sensor. The options are:
•
Internal: the temperature as measured by the device’s inbuilt sensor.
•
Remote: if a remote RTD PT1000 sensor is connected, the temperature is measured by
the remote sensor.
•
Min, Max and Average: if a remote sensor is connected, the measured temperature can
be a calculated using a minimum, maximum or average reading of the two sensors.
Select to save your changes.
13.4. Input and Output values
Screen [2/2] of the In/Out
menu summarises all of
the values and states of the
device’s inputs and outputs.
These values are refreshed
every second.
14.1. 2-pipe fan coil with ECM fan and electrical actuator
14. Applications and connection diagrams
HOME > MENU > ADVANCED > PARAMETERS [1/4]
Application type:
2-pipe system
Control sequence:
Cooling only
Heating
only
Cooling
or
heating
Fan motor type:
EC motor
1
speed
motor*
3
speed
motor*
*use only with FC-RB fan coil driver
HOME > MENU > ADVANCED > IN/OUT [1/2]
Binary input:
Window
contact
Presence
sensor
RTD Sensor Function:
Changeover
sensor
Remote
sensor
Temperature sensor:
Internal
Remote
D1
– C35-FC
M1
– ECM fan (DC 0-10 V)
V1
– Heating or cooling valve actuator (DC 0-10 V)
S1
– Switch for window or presence sensor contact
T1
– Changeover or remote temperature sensor (PT1000)
The C35-FC supports the following applications, which can be confi gured in
Advanced menu.
AO1
AO2
24V
GND
G
D-
D+
GND
GND
RTD
RTD
BIN1
GND
24V
AC/DC
/+
/-
M1
V1
S1
D1
T
T1
6A
Figure 14.1.1. Functional
diagram
Figure 14.1.2. Connection
diagram