22
C35-FC
MS/TP MAC
: The unique MAC address, which can have a value between 0-127 on the local
MS/TP data bus.
Max Master
: The highest MAC address used by BACnet devices in the local MS/TP data bus
(limited to 127). For optimal network performance, limit the Max Master value to the total
number of devices on the data bus.
Max Info Frames
: The maximum number of requests a device is able to send over the local
network. For optimal network performance, this value should be set to 1.
Baud Rate:
The Baud Rate setting determines the rate at which data is sent on the data bus.
The maximum value will be determined or limited by the quality of cabling between the two
furthest devices on the network.
NOTE
: All devices must be set on the same Baud Rate. The available options are:
•
9600
•
19200
•
38400
•
57600
•
76800
(default
value)
Once the desired settings have been selected, press the button to save any changes.
12.1. Network
Enter the
Advanced Settings
menu. Select the
Parameter
button to enter the specifi c
parameters of the system
into the device.
NOTE
: You will be prompted
for a pass code prior to
entering the
Advanced menu.
Enter the passcode to proceed
to the menu. Note: The default
password is 0000.
12. Advanced Menu
NOTE
: BACnet and network
settings should be confi gured
by qualifi ed profesionals.
Device Name
: The device
name that will be used on
the BACnet network.
Device ID
: A unique BACnet
device number which can
have a value between 0 to
HEX 3FFFFF. This will be used
for the device’s identifi cation
on the different protocols
within the BACnet network.
12.1.1. Network [1/2] Network BACnet settings