Preparing the PROCESSOR for Installation
5B6339 – January 1996
11
Installing the PROCESSOR Through a Wall — Feed End
Note
• For Dryer End installation through the wall, see
Page
• The customer is responsible for preparing a hole in
the wall of the correct size to install the
PROCESSOR. Refer to the Site Specifications,
Publication Part No. 5B6338
Caution
Do not stretch the LIGHTTIGHT GASKET.
[1] Install the self-adhesive LIGHTTIGHT GASKET
onto the feed end of the PROCESSOR.
(a) Cut strips of GASKET for the 3 edges of the
PROCESSOR. See the figures.
(b) Cut 2 strips of GASKET for the top and
bottom of the BAR.
[2] Move the PROCESSOR within approximately
2.5 cm (1 in.) of the wall.
[3] Install the 4 FLOOR PLATES under the
4 LEVELING SCREWS. FLOOR PLATES are
available for the 3/8-in. LEVELING SCREWS only.
If installing a SEISMIC KIT, use the FLOOR
PLATES provided with the SEISMIC KIT.
[4] Check that the LIGHTTIGHT GASKET is tight
against the wall. Compress the LIGHTTIGHT
GASKET to approximately 10 mm (3/8 in.).
[5] Wait to place the BAR under the PROCESSOR
until after you level the PROCESSOR on Page
[6] Check for light leakage around the PROCESSOR,
then advance to Page
2.5 cm
(1.0 in.)
H148_0034CA
H148_0034CCA
GASKET
LIGHTTIGHT
BAR
GASKET
LIGHTTIGHT
BAR
PLATE
FLOOR
LEVELING SCREW
WALL
PROCESSOR
GASKET
TIGHT
LIGHT
H148_0035AA
H148_0035ACA
BAR
LIGHTLOCK
GASKET
LIGHTTIGHT
PANEL
WALL