Operating manual PxtRX active energy management device
V1.1DE/EN
19
5
Commissioning
English
Fig. 8: DC circuit (DC link) connection
Determine the polarity of the DC circuit (DC link) connections.
De-energise the DC circuit (DC link).
Ensure that there is no voltage in the DC circuit (DC link).
If accelerated unloading is desired, consultation with Michael Koch GmbH is
required.
Make sure there is no voltage between terminal "Drive +" (X1, pin 1) and terminal
"Drive -" (X1, pin 2).
Connect the negative pole at the DC circuit (DC link) output of the application in
loop through the ferrite sleeve
to "Drive -" (X1, pin 2) on the active energy
management device.
Connect the positive pole at the DC circuit (DC link) output of the application in
loop through the ferrite sleeve
to "Drive+" (X1, pin 1) on the active energy
management device.
Supply the DC circuit (DC link) with voltage.
Connecting two or
more PxtRX active
energy management
device in parallel.
Several PxtRX active energy management devices can also be connected in parallel
via the "Drive +" (X1, pin 1) and "Drive -" (X1, pin 2) terminals on the DC circuit
(DC link).
Please note that PxtRX must always be used with the same settings. All PxtRX energy
management devices must have the same number and storage type of energy
modules or be connected to the same storage unit (DLCM, battery).
In the case of parallel connection, the devices must always be connected to each
other via the K-Bus communication interface (