Commissioning
English
5.1
Earthing the PxtFX active energy management device
Fig. 8: Earthing connection (on the top of the housing)
Earth the PxtFX energy management device on the earthing connection
q
(ring or
forked cable lug M5) (wire cross-section to your national standards).
Perform safety test according to DGUV V2 (German Statutory Accident Insurance).
5.2
Connecting the PxtFX active energy management device
The active PxtFX energy management device may only be operated on a
non
-regenerative application.
In all other cases, Michael Koch GmbH must be consulted immediately - the device
must not be put into operation.
Basic information
• The places of operation must be dry and dust-free.
• The air supplied must not contain any electrically-conductive dust, gas or vapour
which could impair functionality. Corresponding remedial measures must be taken
if necessary.
• The PxtFX active energy management device may only be operated in ambient
temperatures from 0…40° C. High air humidity and condensation must be
excluded.
• The PxtFX active energy management device can only be operated in conjunction
with an application with direct access to the DC circuit capacity (DC link capacity)
(low inductive connection without disconnection device).