10. NRM Parameter table
Pxx Parameter name
d
c
b
a
00
Engineering system,
dimensions
DEMO mode
0 = Normal mode
1 = Demo mode
Engineering system:
0 = EU
1 = US
Dimension:
(EU) 0 = m, 1 = cm, 2 =
mm
(US) 0 = ft, 1 = inch
01
Source of Primary Value
(PV)
0 = DIST, 1 = LEVEL,
2 = VOLUME, 3 = MASS
02
Selectable dimensions
Time units:
0= sec
1= min
2= hour
3=day
(VOL/F-EU)
0 = m
3
, 1=liter
(VOL/F-US)
0 = ft
3
, 1 = US gallon
(MASS-EU)
0 = tonne, 1= US tonne
(MASS-US)
0 = tonne, 1 =lb(pound)
Temperature unit:
0=
C
04
Max. measuring distance
Maximal measuring distance of the level transmitter can be defined
05
Blocking / DEAD ZONE
Minimal measuring distance within the ignores all the measurement values
08
Fix current output
Fix forced value on the output current between 3.8 and 20.5 mA for loop current measuring purposes (operation mode =
manual)
10
4 mA
Measured and transmitted value (PV) assigned to 4 mA current value
11
20 mA
Measured and transmitted value (PV) assigned to 20 mA current value
12
Output current mode
Operation mode:
0= AUTO
1= MANUAL
Error indication
of the current output:
0= HOLD
1= 3.8mA
2= 22mA
19
HART polling address
HART Short Address of the level transmitter (0-15)
20
Damping time
Damping time of the accurate transmitted (displayed) value in sec. after a high fluctuation in the measured value (0-999
25
Echo selection in the measuring windo
0 = AUTO
1= FIRST
2= HIGHEST AMPLITUDE
3= LAST
26
Filling speed
Rate of change of the measured value (when distance is decreasing) which can be just followed with the level transmitt
27
Emptying speed
Rate of change of the measured value (when distance is increasing) which can be just followed with the level transmitte
29
Threshold value
Threshold limit value (0 - 6 dB) for the received echo evaluation
32
Specific gravity of the medium
Data for mass calculation
35
Background mode
Calculating with the saved background
image:
0= OFF
1= ON
40
Tank shape
0 = Standing cylindrical tank with dome
bottom
1 = Standing cylindrical tank with conica
bottom
2 = Standing rectangular tank with or
without chute
3 = Lying cylindrical tank
4 = Spherical tank
41-45
Tank dimensions
47
VMT mode
Operation of the linearization:
0 = OFF, 1 = ON
60 Overall
runtime
Elapsed overall operating hours of the level transmitter (working time) with 0.1 hour accuracy. Service data
61
Runtime after last reset
Elapsed operating hours of the level transmitter since the last turning ON with 0.1 hour accuracy. Service data
70
Number of echoes
Service data
71
Position of the measuring window
Service data
74 Signal-to-noise
ratio
Service data
75
Blocking distance value
Service data
80 Current
output
test
Fix forced value on the output current between 3.8 and 20.5 mA for checking the accuracy of the current generator
Summary of Contents for NRM
Page 1: ...Operating Instructions for Non Contact Radar Level Transmitter Model NRM...
Page 43: ...NRM NRM K06 0422 page 43 20 ATEX certificate...
Page 44: ...NRM page 44 NRM K06 0422...
Page 45: ...NRM NRM K06 0422 page 45...
Page 46: ...NRM page 46 NRM K06 0422...
Page 47: ...NRM NRM K06 0422 page 47...
Page 48: ...NRM page 48 NRM K06 0422...
Page 49: ...NRM NRM K06 0422 page 49...
Page 50: ...NRM page 50 NRM K06 0422 21 IECEx certificate...
Page 51: ...NRM NRM K06 0422 page 51...
Page 52: ...NRM page 52 NRM K06 0422...