Volume / Mass table
Parameter:
-
Path:
CALCULATION / V/M CALC. MODE / V/M TABLE
Description:
VIEW/EDIT TABLE
ADD ITEM
DELETE ITEM
If none of the formulas match perfectly to the characteristics of the
needed tank, there is a possibility to use table calculation mode. The
device can handle a 99-point table on this purpose and counts values
between the neighbouring point pairs with linear interpolation.
The input (left) side of the table contains the level data, the output (right)
side contains the volume or mass data.
The first point pair of the table should be 0,0. If a long table wanted to be
shortened, 0,0 point pair should be entered into the last item of the table
and the device modifies the unused point pairs automatically in the
background
to
0,0.
The status (ON or OFF) of the table is shown on a warning message (1)
on the bottom line of the display.
V/ M TABLE
V/ M CALC . MODE
TANK FUNCTION /SHAPE
VMT IS ACTIVE
1
All modifications are done on a temporary table. This temporary table
becomes valid after exiting.
Modifications during the programming procedure have no effect on the
measurement and the transmitting.
Entering the point pairs can be done in arbitrary order, because the
device sorts according to ascending order. Both sides of the table have
to be strictly monotonic increasing. In case of any error, warning
message (see: 9
th
chapter) will appear. When entering again the table
an inscription indicates the first wrong line.
View table:
In VIEW/EDIT TABLE menu point items of the ordered table can be
checked. For moving in the list use the and buttons, for editing the
selected item use the
E
button. Exiting from the list can be done by
pressing the button.
01: 0000 .0 000000 .000
EDIT/VIEW TABLE
02: 0100 .0 000100 .000
Edit table:
Adding a point pair (ADD ITEM) to the list or pressing
E
button on an
existing item, an edit screen will appear. In this edit screen there are two
editing filed. Both editing field works as same as editing a parameter.
Getting from the first field to the second field press the
E
button.
Pressing
E
button in the second field will return back to the previous
menu point. When exiting from the last field, the device performs the
ordering of the table.
LEVEL VALUE : cm
02. VM TABLE ITEM
095310.000
0012.0
0
V/M VALUE : m
3
Delete item
Moving in the list can be done with and buttons, for deleting an item
press the
E
button on the selected item. Exiting from the list can be
done by pressing the button. The table should contain at least 2 items.
01: 0000 .0 000000 .000
DELETE ITEM
02: 0100 .0 000100 .000
Summary of Contents for NRM
Page 1: ...Operating Instructions for Non Contact Radar Level Transmitter Model NRM...
Page 43: ...NRM NRM K06 0422 page 43 20 ATEX certificate...
Page 44: ...NRM page 44 NRM K06 0422...
Page 45: ...NRM NRM K06 0422 page 45...
Page 46: ...NRM page 46 NRM K06 0422...
Page 47: ...NRM NRM K06 0422 page 47...
Page 48: ...NRM page 48 NRM K06 0422...
Page 49: ...NRM NRM K06 0422 page 49...
Page 50: ...NRM page 50 NRM K06 0422 21 IECEx certificate...
Page 51: ...NRM NRM K06 0422 page 51...
Page 52: ...NRM page 52 NRM K06 0422...