NEO 01/0820
Rev A
7
|
Introduction
Step One
INTRINSICALLY SAFE CONTROL DRAWING
(NEO-7006-IS & NEO-7012-IS ONLY):
Intrinsically Safe Approvals:
Intrinsic Safe:
14-28 Vdc
22mA
Output:
4-20mAdc
Temp:
-40°C to +80°C
Type 4X/IP66:
US06 series
Approval Agency:
c
CSA
us
General:
CE,
RoHS
Intrinsically Safe Entity Parameters:
U
i
/V
max
= 28 VDC
I
i
/I
max
= 100 mA
P
i
= 840 mW
L
i
= 2.46 mH
C
i
= 0
μ
F
CSA for U.S.:
Class I, Div 1, Groups A, B, C and D T4;
Class II, Div 1, Groups E, F, G T4;
Class III, T135°C;
Class I, Zone 0, IIC AEx ia T4 Ga,
Class II, Zone 20, IIIC AEx ia, T135°C, Da
CSA for Canada:
Class I, Division 1, Groups A, B, C and D T4;
Class II, Division 1, Groups E, F, G T4;
Class III, T135°C;
Ex ia IIC T4 Ga;
Ex ia IIIC T135°C Da;
IECEx:
Ex ia IIC T4 Ga;
Ex ia IIIC T135°C Da
Tamb: -40°C to 80°C
Install as per Control Drawing 600820