SPECIFICATIONS
Electrical:
Supply Voltage:
14-28 Vdc
Signal:
4 to 20 mA current loop; 22 mA
max.
Signal invert:
4-20mA or 20-4mA
Signal fail-safe:
4mA, 20mA, 21mA, 22mA or
hold last value
Mechanical:
Display Module:
Removable via short cable and
plug
LCD:
6 characters, 10 mm (0.394”)
height
Buttons:
Three, UP / OK / DN
Pin Connection: Display can be removed such
that the open connection allows
the sensor to be NEOCal
software capable.
Enclosure:
General Purpose: Polypropylene head with skirt to
support transducer w/ conduit
Intrinsically Safe:
Aluminum thermal head with
skirt to support transducer w/
conduit. * Earth ground on
package external (min. 14
AWG)
Electrical Connections:
Power & Return:
2-pin quick connect terminal
block
NEOCal Connect.: 2-pin quick connect terminal
block
Display Connect.: 5-pin plug & socket
Conduit Connection: Single, 1/2 inch NPT
Transducer:
Black, Polyvinylidene Fluoride
(PVDF)
Terminal Cable Size: 16 to 24 AWG
Process Mount:
-7006: 2" NPT
-7012: 3” NPT
Compliance:
CE,
RoHS
Environmental:
Temperature:
F: -40° to 176°
C: -40° to 80°
Temp. compensation: Automatic
Ambient temp.:
F: -31° to 140°
C: -35° to 60°
Pressure:
30 psi (2 bar)
Enclosure:
General
purpose: IP68
Intrinsically
safe:
IP66
Functional:
Range:
-7006: 6.0m (19.69 feet)
-7012: 12.0m (39.4 feet)
Dead band:
-7006: 20cm (8 inches)
-7012: 45.7cm (18 inches)
Accuracy:
0.2% of Range in air at 20 °C
Resolution:
-7006: 2mm (0.079 inches)
-7012: 5mm (0..196 inches)
Beam width:
-7006:7.6cm (3 inches)
-7012: 15.2cm (6 inches)
Menu: