NEO 01/0820
Rev A
11
|
Getting Started
Step Two
NEOCAL SOFTWARE VS. DISPLAY CONFIGURATION
NEO-7 can be configured using either the free NEOCal software and USB
®
Fob or with the internal display
module. Either method will accomplish the goal of sensor configuration. Changes to the configuration can be
made using the alternative method. Upon implementing one methodology, it is recommended to complete the
configuration before using the other methodology in making any adjustments.
NEO-7 can be configured before installation or after installation. The transmitter features non-volatile memory,
so any settings configured before installation will not be lost when the sensor is powered down. To start, the
following information is required:
Basic Tank Information
o
HEIGHT
(Sensor Height) – Distance from
the bottom of the tank to the bottom of the
sensor.
o
FILL-H
(Fill-Height) – Distance from the
bottom of the tank to the fill-height of the
liquid.
Power:
o
Provide input power to the NEO-7
Note: The HEIGHT and Fill-Height (FILL-H) settings also determine the 4 to 20 mA current span. The
HEIGHT setting determines the 4mA position and the FILL-H setting determines the 20 mA position.