background image

14

Parameter setting

Sensor KNX AQS-UP basic

 • from software 3.1 • Status: 24.03.2016 • Technical changes reserved. Errors reserved.

4.2.

General settings

Set the basic data transfer characteristics and select whether or not malfunction ob-
jects should be sent. 

4.3.

CO2 measured value 

Use 

Offsets

 to adjust the readings to be sent.

The unit can calculate a 

mixed value

 from its own reading and an external value. Set

the mixed value calculation if desired.

Note:

 if an external portion is used, all of the following settings (threshold values, etc.)

are related to the overall reading!

The 

maximum readings

 can be saved and sent to the bus. Use the "Reset CO

2

 max.

value" object to reset the value to the current reading.

Note: 

The values are not retained after a reset.

Send delay after power-up and programming for:

Measured values

5 s • ... • 2 h

Threshold values and switching outputs

5 s • ... • 2 h

Controller objects

5 s • 10 s • ... • 2 h

Logic outputs

5 s • 10 s • ... • 2 h

Maximum telegram quota

• 1 message per second 
• ... 
• 5 messages per second 
• ... 
• 20 messages per second

Use CO2 malfunction object

Yes • No

Offset in ppm

-100...100; 0

Use external reading

Yes • No

Ext. Reading proportion of the total reading

5% • 10% • ... • 50% • ... • 100%

Send internal and total reading

• never
• periodically
• On change 
• on change and periodically

From change of

(if sent on change)

2% • 5% • 10% • 25% • 50% (relative to the 
last reading)

Send cycle

(if sent periodically)

5 s • ... • 2 h

Use maximum value

Yes • No

Summary of Contents for AQS-UP basic

Page 1: ...Installation and Adjustment KNX AQS UP basic Air Quality Sensor Article numbers 70224 white 70225 aluminium 70226 anthracite 70227 stainless steel EN...

Page 2: ...ssembly of the sensor 7 2 5 Notes on mounting and commissioning 7 3 Transfer protocol 9 3 1 List of all communications objects 9 4 Parameter setting 13 4 1 Behaviour on power failure restoration of po...

Page 3: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Page 4: ...own measured value and external value proportions can be set in percentage PI controller for ventilation depending on CO2 concentration dehumidification humidification one step or dehumidification one...

Page 5: ...period After this the CO2 sensor will recalibrate every two weeks by defining the lowest meas ured value captured during that period without interruption of the bus voltage as a reference for fresh a...

Page 6: ...be used for its intended purpose Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediate...

Page 7: ...om ducts which lead from other rooms or from the outside to the junction box in which the sensor is mounted Measurement variations from such sources of interference must be corrected in the ETS in ord...

Page 8: ...e metal frame so that sensor and frame are fixed 2 5 Notes on mounting and commissioning Never expose the device to water e g rain or dust This can damage the electronics You must not exceed a relativ...

Page 9: ...8 Installation and commissioning Air Quality Sensor KNX AQS UP basic Version 24 03 2016 Technical changes reserved Errors reserved...

Page 10: ...ut 9 008 C R T 101 CO2 maximum value request Input 1 017 C W 102 Maximum CO2 reading Output 9 008 C R T 103 Reset CO2 maximum value Input 1 017 C W 104 CO2 threshold value 1 Absolute value Input Outpu...

Page 11: ...hreshold value 4 Absolute value Input Output 9 008 C R W T U 123 CO2 threshold value 4 1 0 Input 1 002 C W 124 CO2 threshold value 4 Switching delay from 0 to 1 Input 7 005 C W 125 CO2 threshold value...

Page 12: ...le Input 5 Input 5 010 C W 147 Comparator 2 actuating variable Out put Output 1 001 C R T 148 Comparator 2 actuating variable Block Input 1 002 C W 149 AND logic 1 1 bit switching output Output 1 002...

Page 13: ...ut Output 1 002 C R T 182 OR logic 1 8 bit output A Output 5 010 C R T 183 OR logic 1 8 bit output B Output 5 010 C R T 184 OR logic 1 Block Input 1 002 C W 185 OR logic 2 1 bit switching output Outpu...

Page 14: ...5 010 C R T 207 OR logic 7 8 bit output B Output 5 010 C R T 208 OR logic 7 Block Input 1 002 C W 209 OR logic 8 1 bit switching output Output 1 002 C R T 210 OR logic 8 8 bit output A Output 5 010 C...

Page 15: ...be saved and sent to the bus Use the Reset CO2 max value object to reset the value to the current reading Note The values are not retained after a reset Send delay after power up and programming for...

Page 16: ...hold value must be defined which will be valid un til the 1st communication of a new threshold value For units which have already been taken into service the last communicated threshold value can be u...

Page 17: ...LV above 1 LV hysteresis below 0 LV above 0 LV hysteresis below 1 LV below 1 LV hysteresis above 0 LV below 0 LV hysteresis above 1 Delays can be set via objects in seconds No Yes Switching delay fro...

Page 18: ...is setting The status object shows the current status of the output variable 0 OFF 0 ON and can for example be used for visualisation Switching output sends on change Do not send message Send switchin...

Page 19: ...e limit A set target value will be retained until a new value or a change is transferred The cur rent value is saved in EEPROM so that this is retained in the event of a power supply failure and will...

Page 20: ...longer until the necessary variable for the target value deviation is reached You should set the time appropriate to the ventilation system at this point follow the manufacturer s instructions Now det...

Page 21: ...ri odically Send cycle is only sent if periodically is selected 5 s 10 s 30 s 5 min 2 h From change of is only sent if on change is selected 1 2 5 10 20 25 Analysis of the blocking object at value 1 b...

Page 22: ...ue 0 1 Logic output sends two 8 bit objects Type of objects Value 0 255 Percent 0 100 Angle 0 360 Scenario load 0 127 if logic 1 object A value Setting dependent on type of object if logic 0 object A...

Page 23: ...do not send message send value for logic 0 send value for logic 1 Value of the parameter Send behaviour Settings options Behaviour of the switching output on release on change of logic do not send me...

Page 24: ...tput CO2 3 Switching output CO2 3 inverted Switching output CO2 4 Switching output CO2 4 inverted CO2 controller status ventilation 1 CO2 controller status ventilation 1 inverted CO2 controller status...

Page 25: ...24 Parameter setting Sensor KNX AQS UP basic from software 3 1 Status 24 03 2016 Technical changes reserved Errors reserved AND logic output 8 inverted...

Page 26: ...GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner elektronik de Technical support 49 0...

Reviews: