Air Quality Sensor KNX AQS-UP basic
• Version: 24.03.2016 • Technical changes reserved. Errors reserved.
1.1. Technical specifications
* Mind the notes on
Accuracy of the measurement
, page 4
The product conforms with the provisions of EU guidelines.
1.1.1. Accuracy of the measurement
Measurement variations from sources of interference (see chapter
Installation posi-
tion
) must be corrected in the ETS in order to ensure the specified accuracy of the sen-
sor (offset). To ensure a correct CO
2
measurement, the device must be installed in a
windproof socket.
The indicated
accuracy of the CO
2
measurement
will be achieved after a run-in pe-
riod of 24 hours (without interruption of the bus voltage) if the sensor has been in con-
tact with fresh air (350…450 ppm) at least once in this period.
After this, the CO
2
sensor will recalibrate every two weeks by defining the lowest meas-
ured value captured during that period (without interruption of the bus voltage) as a
reference for fresh air.
Housing
Plastic material (partly lacquered)
Colours
• White glossy (similar to RAL 9016 Traffic White)
• Aluminium matt
• Anthracite matt
• Stainless steel
• Special colours on request
Mounting
In-wall (in socket
Ø
60 mm, 42 mm deep)
Protection category
IP 20
Dimensions
Housing approx. 55 x 55 (W x H, mm),
mounting depth approx. 15 mm,
base plate approx. 71 x 71 (W x H, mm)
Total weight
approx. 72 g
Ambient temperature
Operation -10…+50°C, storage -20…+60°C
Ambient air humidity
max. 95% R. H., avoid bedewing
Operating voltage
KNX bus voltage
Bus current
max. 10 mA
Data output
KNX +/- bus terminal plug
BCU type
Own micro controller
PEI type
0
Group addresses
max. 254
Allocations
max. 254
Communication objects
133
CO
2
measurement range
0...2000 ppm
CO
2
resolution
1 ppm
CO
2
accuracy*
± 50 ppm ± 3% of the measured value