Figure 6-3 Pressure Drop vs. Flow
Table 6A - Boiler Flow Requirements
Temperature Rise and Head Loss Based on Boiler Output in Btu/hr
Model
Minimum
Pipe Ø
Factory
Provided
Circulator
20°F
25°F
35°F
Maximum
Flow
Minimum Flow
High Fire
Low Fire
56
1"
UPS 15-58 FC
3.0 gpm 0.1 ft/hd 4.2 gpm 0.2 ft/hd 5.2 gpm 0.3 ft/hd 17.0 gpm 3.1 ft/hd
2.1 gpm
1.0 gpm
86
1"
UPS 15-58 FC
4.6 gpm 0.3 ft/hd 6.5 gpm 0.6 ft/hd 8.1 gpm 1.0 ft/hd 17.0 gpm 4.3 ft/hd
3.2 gpm
1.0 gpm
111
1"
UPS 15-58 FC
6.0 gpm 0.5 ft/hd 8.4 gpm 1.1 ft/hd 10.5 gpm 1.7 ft/hd 17.0 gpm 4.4 ft/hd
4.2 gpm
1.0 gpm
156
1"
UPS 15-58 FC
8.4 gpm 1.5 ft/hd 11.8 gpm 2.9 ft/hd 14.7 gpm 4.5 ft/hd 17.0 gpm 6.0 ft/hd
5.9 gpm
1.0 gpm
200
1-1/4"
UPS 26-99 FC
10.9 gpm 0.4 ft/hd 15.2 gpm 0.7 ft/hd 19.0 gpm 1.1 ft/hd 27.0 gpm 2.3 ft/hd
7.6 gpm
1.5 gpm
286
1-1/4"
UPS 26-99 FC
15.5 gpm 0.8 ft/hd 21.7 gpm 1.6 ft/hd 27.0 gpm 2.4 ft/hd 27.0 gpm 2.4 ft/hd
10.8 gpm
1.5 gpm
400
1-1/2"
UPS 26-99 FC
21.7 gpm 0.5 ft/hd 30.4 gpm 0.9 ft/hd 38.0 gpm 1.4 ft/hd 38.0 gpm 1.4 ft/hd
15.2 gpm
4.5 gpm
Reference Table 6B for pump speed selection.
6
Hydronic piping
(continued)
Pump sizing and flow requirements are based on 20 feet of piping, 4 - 90° elbows, and 2 - fully ported ball
valves.
0.0 gpm 2.0 gpm4.0 gpm 6.0 gpm 8.0 gpm10.0 gpm 12.0 gpm
14.0 gpm16.0 gpm18.0 gpm20.0 gpm
22.0 gpm24.0 gpm26.0 gpm28.0 gpm30.0 gpm
Head (ft.)
Head (ft.)
0.0 gpm 2.0 gpm4.0 gpm 6.0 gpm 8.0 gpm 10.0 gpm12.0 gpm
14.0 gpm16.0 gpm18.0 gpm20.0 gpm22.0 gpm24.0 gpm26.0 gpm28.0 gpm30.0 gpm
Head (ft.)
0.0 gpm
5.0 gpm
10.0 gpm
15.0 gpm
20.0 gpm
25.0 gpm
30.0 gpm
35.0 gpm
40.0 gpm
0.0 gpm
2.0 gpm
4.0 gpm
6.0 gpm
8.0 gpm
10.0 gpm
12.0 gpm
14.0 gpm
16.0 gpm
18.0 gpm
20.0 gpm
Head (ft.)
NOTICE
NOTICE