Installation & Operation Manual
3
General
venting
(continued)
17
Requirements for installation in
Canada
1. Installations must be made with a vent pipe system
certified to ULC-S636.
2. The first three (3) feet of plastic vent pipe from the
appliance flue outlet must be readily accessible for visual
inspection.
3. The components of the certified vent system must not be
interchanged with other vent systems or unlisted
pipe/fittings. For concentric vent installations, the inner
vent tube must be replaced with field supplied certified vent
material to comply with this requirement.
4. The 2", 3" and 4" Concentric Vent Kit available from
Lochinvar (see Section 4 –
Sidewall Termination – Optional
Concentric
Vent
) and the 2", 3" and 4" Concentric Vent Kit
available from IPEX are both approved for use on the
Knight Wall Hung Fire Tube boiler. Both kits are listed to
the ULC-S636 standard for use in Canada.
Vent
Diameter
Vent
Supplier
Vent
Material
Part Number
2 inch
Lochinvar
PVC
100140485
3 inch
Lochinvar
PVC
100269005
4 inch
Lochinvar
PVC
100140484
2 inch
IPEX
PVC
196005
3 inch
IPEX
PVC
196006
4 inch
IPEX
PVC
196021
3 inch
IPEX
CPVC
197009
4 inch
IPEX
CPVC
197021
Table 3B Approved Concentric Vent Systems
Sizing
The Knight Wall Hung Fire Tube boiler uses model specific
combustion air intake and vent piping sizes as detailed in Table
3A below.
Model
Inlet
Diameter
Vent
Diameter
Maximum
Length
56
2 inches / 3 inches 2 inches / 3 inches 80 feet / 100 feet
86
2 inches / 3 inches 2 inches / 3 inches 50 feet / 100 feet
111
2 inches / 3 inches 2 inches / 3 inches 40 feet / 100 feet
156
3 inches
3 inches
100 feet
200
3 inches
3 inches
100 feet
286
3 inches / 4 inches 3 inches / 4 inches 50 feet / 100 feet
400
4 inches
4 inches
100 feet
Table 3A Air Intake/Vent Piping Sizes
Increasing or decreasing combustion air or
vent piping sizes is not authorized.
NOTICE
When determining equivalent combustion air and vent
length, add 5 feet for each 90° elbow and 3 feet for each 45°
elbow.
EXAMPLE:
20 feet of PVC pipe + (4) 90° (2)
45° (1) concentric vent kit (100269005) = 49
equivalent feet of piping.
For Models 56 - 111 using 2" venting
and Model 286 using 3" venting, the first
seven (7) equivalent feet of vent must be
CPVC or polypropylene (field supplied).
This includes any transition piece used to
increase or decrease the vent diameter.
NOTICE
The minimum combustion air and vent
piping length is 12 equivalent feet.
NOTICE
The appliance output rating will reduce
by up to 2.3% for each 25 feet of vent
length. Consult factory to determine
de-rate values.
NOTICE