69
Specifications
ProLine P51*00 Input
Measuring range limits 30 mV ... 125 V
Linear up to 120 % of range
Meas. range (±)
Overload capacity
±5 V
30 mV ... 300 mV
±80 V
300 mV ... 12.5 V
±200 V
Short-time (1 s)
±300 V
12.5 V ... 125 V
Input resistance
100 kΩ
30 mV ... 200mV
70 ... 100 kΩ
200 mV ... 12.5 V
360 kΩ
12.5 V ... 125 V
Input capacitance
< 3.3 nF
30 mV ... 12.5 V
< 10 nF
12.5 V ... 125 V
ProLine P52*00 Input
Measuring range limits 100 V … 4200 V ProLine P52100
unipolar/bipolar,
linear up to 120 % of range,
max. ±4800 V DC
100 V … 1800 V ProLine P52000
unipolar/bipolar,
linear up to 120 % of range,
max. ±2000 V DC
Overload capacity
±1350 V
Short-time (1 s)
±2700 V
100 ... 900 V
ProLine P 52000
±2000 V
Short-time (1 s)
±3400 V
750 ... 1800 V
ProLine P 52100
±4800 V
Short-time (1 s)
±7100 V
750 ... 4200 V
Input resistance
> 2 MΩ
100 ... 900 V
10 MΩ
900 ... 4200 V
Input capacitance
< 10 pF
100 V ... 4200 V
Output
Current output
± 20 mA
linear up to
±24 mA
a)
max.
±30 mA
0(4) ... 20 mA
linear up to
±24 mA
a)
max.
±30 mA
± 40 mA
linear up to
±40 mA
max.
±48 mA
(optional)
0(4) ... 40 mA
Linear up to
40 mA
max.
±48 mA
(optional)
Burden
(±) 0(4) ... 20 mA 600 Ω
Linear up to 12.6 V
a) Burden 500 Ω max., with 600 Ω burden: linear up to ± 21 mA,
for P52000 with product option E (energy measurement): linear up to ± 26 mA