FDSD smoke control damper is always tested in standardized
support frames in accordance with EN 1366-2: 2015. The results 
obtained are valid for all similar support frames which have a 
thickness/density/fire resistance similar or greater than the one 
of the tests.

The duct connected to the smoke control damper must be 
supported or hung in such a way that the damper does not carry 
its weight. The damper must not support any part of the 
surrounding construction or wall which could cause damage 
and consequent damper failure. The damper driving mechanism 
can be placed on either side of the wall, however it needs to be 
placed so as to ensure easy access during inspection.

The smoke control damper must be installed into a fire partition
structure in such a way that the damper blade in its closed
position is located inside this structure.

The gap in the installation opening between the smoke control 
damper and the wall can be increased by up to 50% of the 
gap dimension, or decreased to the smallest dimension 
(B + 80 x H + 80)

• 

The installation must comply with the tests that were

       performed during certification

• 

The FDSD smoke damper can be connected to ducts that 
have been tested to EN 1366-9 and EN 1366-8. Also, the 
smoke damper can be connected to fire-resistant ducts 
that have been tested to EN 1366-1

• 

Avoid any obstruction of the moving blade by the 

       connected ducts

• 

The class of air-tightness is maintained in case the 

       installation of the damper is made in accordance with the     
       technical manual

• 

For indoor use only

• 

If the damper is installed in a wall of a lower fire resistance 
class, the damper itself will have a lower fire resistance 
class

All dampers have to be installed with the blade axis in a 
horizontal position. To help you find the suspension plane, a 
bendable fixing bracket is provided on the damper casing and 
the red tape is placed on the casing to mark the location of 
the wall limit 

WALL LIMIT

125 mm

(distance from wall limit to the end of smoke control damper 
is 125 mm).

 

Check the operation of the smoke control 

damper before commencing the installation!

Summary of Contents for FDSD

Page 1: ...r Croatia 385 0 1 33 62 513 info klimaoprema com www klimaoprema com Projektiranje proizvodnja i odr avanje opreme za klimatizaciju ventilaciju i iste prostore Design production and service of Ventila...

Page 2: ...and elastomer rubber Smoke control dampers FDSD are produced in sizes from 200x200 till 1500x800 mm FDSD dampers are equipped with Belimo actuator drives in 24 V or 230 V versions Activation of smoke...

Page 3: ...the dampers blade is acceptable Fire resistance of smoke control damper depends on classification of walls It is allowed to install products to walls only according to products Declaration of Performa...

Page 4: ...steel sheet but on demand can be produced out of Galvanized steel and powder coated Stainless steel EN 1 4301 EN 1 4491 EN 1 4404 AISI 304 316 316L Stainless steel and powder coated EN 1 4301 EN 1 44...

Page 5: ...CATIONS MODULES REPLACEMENTS MAINTENANCE AND OPERATION FDSD DIMENSIONS Length of damper blade outside of casing X H 2 175 mm Actuator A mm C mm D mm E mm BEN M 25 200 90 120 BEE M 25 225 100 120 B 60...

Page 6: ...31 6 33 5 35 5 37 4 39 3 41 3 43 2 45 2 47 2 49 1 51 0 52 9 54 9 56 8 58 7 60 6 62 6 64 5 66 4 Pressure drop tables ZETA VALUES FDSD H B 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950...

Page 7: ...lation opening between the smoke control damper and the wall can be increased by up to 50 of the gap dimension or decreased to the smallest dimension B 80 x H 80 The installation must comply with the...

Page 8: ...ke control ductwork and or may be installed in a fire compartment structure Single compartment smoke control dampers EN 12101 8 Smoke control dampers for use in single compartment areas which may be a...

Page 9: ...n of performance www klimaoprema com fdsd dop Aerated concrete 450 kg m3 or reinforced concrete 2200 kg m3 wall more than 100 mm thick Support for installation with mortar In the smoke control damper...

Page 10: ...r gypsum plaster 1 Recommended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1...

Page 11: ...commended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1 90 Damper blade must...

Page 12: ...ecommended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1 90 Damper blade must...

Page 13: ...moke extract duct 8 Dry wall screw staple Rigid wall installation Duct from one side 1 FDSD smoke damper 2 Gypsum mortar mortar 3 Solid wall 4 Promatect L500 50mm strip 5 Promatect L500 50mm strip 6 P...

Page 14: ...l metal duct 1 Smoke damper 2 Flexible connector 3 Sheet steel smoke extract duct In case of fire there is an expansion of the ducts therefore it is necessary to install a flexible connection for conn...

Page 15: ...termosensor Type of Belimo actuator BEN 24 V BEN 230 V BEE 24 V BEE 230 V Torque 15 Nm 15 Nm 25 Nm 25 Nm Nominal voltage power consumption voltage AC DC 24V 50 60 Hz AC 230 V 50 60 Hz AC DC 24V 50 60...

Page 16: ...utton The dampers can be opened and closed via potential free contact or 24 VAC DC external voltage The master can also be controlled via MODBUS TCP IP and RTU or BACnet IP or MS TP and therefore can...

Page 17: ...plate and rectangular shaft 3 Insert new transition plate and rectangular shaft from ERK kit NOTE A Pay attention to the position of the indicator cut B Pay attention to the indicator cut insert the...

Page 18: ...ntact your supplier STORAGE If the damper is not installed immediately Remove any wrapping Protect smoke control damper from dust and contamination Do not expose the smoke control damper to the effect...

Page 19: ...r Croatia 385 0 1 33 62 513 info klimaoprema com www klimaoprema com Projektiranje proizvodnja i odr avanje opreme za klimatizaciju ventilaciju i iste prostore Design production and service of Ventila...

Reviews: