SMOKE CONTROL DAMPERS

PRODUCT OVERVIEW

DIMENSIONS

INSTALLATIONS

ACTUATORS

COMMUNICATIONS MODULES

REPLACEMENTS

MAINTENANCE AND OPERATION

COMMUNICATION 

MODULES

POWERLINE

•  230 VAC Powerline communication on field side
•  Topology: Free
•  Max. distance between master and slave: 
       1200 m
•  Display of damper position (incl. angle**)
•  Button on device for damper function check
•  Relay outputs for enabling ventilation
•  Optional control and monitoring via Modbus 

RTU (RS-485) or Modbus TCP/IP (Ethernet) 
BACnet MS/TP or BACnet IP

•  Optional monitoring on external computer or on 

control cabinet touch screen 

      (TCP/IP communication)
•  USB interface and CDU software for simple 

configuration and diagnostics at on-site 
computer

•  Event logging

FDSD

FDSD

FDSD

BKN230-24-PL

BKN230-24-PL

BKN230-24-PL

BKS64-PL

BMS

BKS64 - PL 

is a master for up to 64 BKN230-24-PL devices. 

It is a control and display module for motorized fire protection 
dampers or smoke extraction dampers. It communicates with 
the slaves directly via the 230 VAC power cable.
The Powerline slaves (BKN230-24-PL) have a unique physical 
MAC address and can therefore be detected automatically irre-
spective of pre-addressing. Automatic or selective addressing, 
which is primarily for spatial location, can be carried out on the 
slave itself before installation or later during commissioning.
The damper positions and any faults are displayed directly 
on the device. Dampers can be selected and tested with the 
pushbutton. The dampers can be opened and closed via 
potential-free contact or +24 VAC/DC external voltage.
The master can also be controlled via MODBUS (TCP/IP and 
RTU) or BACnet (IP or MS/TP) and therefore can be considered 
as a Modbus/Powerline or BACnet/Powerline Gateway.

Technical documentation BKS

BKN230-24-PL

 

is the link between the 

Powerline Master (e.g. BKS64-PL) and 
the motorized smoke control damper. 
It supplies a conventional spring return 
or a Belimo Top-Line “-ST” actuator and 
optionally an optical smoke detector with 
electrical energy. Communication with 
the master device takes place directly via 
the 230 VAC supply line (POWERLINE 

Powerline

Powerline

Powerline

Powerline

ModBus / BACNet

Power supply

Spring terminal for 230 VAC 2 x 2.5 mm2
installation cable
X1.1 Neutral conductor (N)
X1.2 Phase conductor (L)
Fuse protection:
13 A, characteristic D if less than 32 x BKN230-24-PL
16 A, characteristic D if 32 or more x BKN230-24-PL
(slave fuse:10A, slow-blow)

Powerline output

Spring terminal for 230 VAC installation cable
X1.1 Neutral conductor (N)
X1.2 Phase conductor (L)
Cross section
1.5 mm2
if less than 32 x BKN230-24-PL
2.5 mm2
if 32 or more x BKN230-24-PL
Connect optional shield to earth only at the master end.

technology). The Powerline participants (BKN230-24-PL) 
have a unique physical MAC address and are therefore always 
recognized by the master, regardless of preaddressing or 
automatic addressing by the master.

•  230 VAC Powerline communication with dynamic signal 

adjustment and zero crossing detection

•  Connection for a conventional or Belimo Topline actuator 

(auto recognition)

Technical documentation BKN

COMMUNICATIONS MODULES

Summary of Contents for FDSD

Page 1: ...r Croatia 385 0 1 33 62 513 info klimaoprema com www klimaoprema com Projektiranje proizvodnja i odr avanje opreme za klimatizaciju ventilaciju i iste prostore Design production and service of Ventila...

Page 2: ...and elastomer rubber Smoke control dampers FDSD are produced in sizes from 200x200 till 1500x800 mm FDSD dampers are equipped with Belimo actuator drives in 24 V or 230 V versions Activation of smoke...

Page 3: ...the dampers blade is acceptable Fire resistance of smoke control damper depends on classification of walls It is allowed to install products to walls only according to products Declaration of Performa...

Page 4: ...steel sheet but on demand can be produced out of Galvanized steel and powder coated Stainless steel EN 1 4301 EN 1 4491 EN 1 4404 AISI 304 316 316L Stainless steel and powder coated EN 1 4301 EN 1 44...

Page 5: ...CATIONS MODULES REPLACEMENTS MAINTENANCE AND OPERATION FDSD DIMENSIONS Length of damper blade outside of casing X H 2 175 mm Actuator A mm C mm D mm E mm BEN M 25 200 90 120 BEE M 25 225 100 120 B 60...

Page 6: ...31 6 33 5 35 5 37 4 39 3 41 3 43 2 45 2 47 2 49 1 51 0 52 9 54 9 56 8 58 7 60 6 62 6 64 5 66 4 Pressure drop tables ZETA VALUES FDSD H B 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950...

Page 7: ...lation opening between the smoke control damper and the wall can be increased by up to 50 of the gap dimension or decreased to the smallest dimension B 80 x H 80 The installation must comply with the...

Page 8: ...ke control ductwork and or may be installed in a fire compartment structure Single compartment smoke control dampers EN 12101 8 Smoke control dampers for use in single compartment areas which may be a...

Page 9: ...n of performance www klimaoprema com fdsd dop Aerated concrete 450 kg m3 or reinforced concrete 2200 kg m3 wall more than 100 mm thick Support for installation with mortar In the smoke control damper...

Page 10: ...r gypsum plaster 1 Recommended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1...

Page 11: ...commended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1 90 Damper blade must...

Page 12: ...ecommended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1 90 Damper blade must...

Page 13: ...moke extract duct 8 Dry wall screw staple Rigid wall installation Duct from one side 1 FDSD smoke damper 2 Gypsum mortar mortar 3 Solid wall 4 Promatect L500 50mm strip 5 Promatect L500 50mm strip 6 P...

Page 14: ...l metal duct 1 Smoke damper 2 Flexible connector 3 Sheet steel smoke extract duct In case of fire there is an expansion of the ducts therefore it is necessary to install a flexible connection for conn...

Page 15: ...termosensor Type of Belimo actuator BEN 24 V BEN 230 V BEE 24 V BEE 230 V Torque 15 Nm 15 Nm 25 Nm 25 Nm Nominal voltage power consumption voltage AC DC 24V 50 60 Hz AC 230 V 50 60 Hz AC DC 24V 50 60...

Page 16: ...utton The dampers can be opened and closed via potential free contact or 24 VAC DC external voltage The master can also be controlled via MODBUS TCP IP and RTU or BACnet IP or MS TP and therefore can...

Page 17: ...plate and rectangular shaft 3 Insert new transition plate and rectangular shaft from ERK kit NOTE A Pay attention to the position of the indicator cut B Pay attention to the indicator cut insert the...

Page 18: ...ntact your supplier STORAGE If the damper is not installed immediately Remove any wrapping Protect smoke control damper from dust and contamination Do not expose the smoke control damper to the effect...

Page 19: ...r Croatia 385 0 1 33 62 513 info klimaoprema com www klimaoprema com Projektiranje proizvodnja i odr avanje opreme za klimatizaciju ventilaciju i iste prostore Design production and service of Ventila...

Reviews:

Related manuals for FDSD