SMOKE CONTROL DAMPERS

PRODUCT OVERVIEW

DIMENSIONS

INSTALLATIONS

ACTUATORS

COMMUNICATIONS MODULES

REPLACEMENTS

MAINTENANCE AND OPERATION

Rigid wall installation

(gypsum plaster / 
mortar sealing) 

Duct from one side

Rigid wall (aerated concrete, reinforced concrete,
gypsum blocks, etc.) with minimum density of 
450 kg/m³ and minimum thickness of 100 mm. 
Installation material: mortar or gypsum plaster.

1. Recommended wall opening for the damper 
installation is B (H) + 80 mm or more 
(up to 50% more). Insert damper into wall to the 
wall limit mark 

(7)

 on the damper and bend the 

fixing bracket 

(1)

 90°.

Damper blade must be closed during the 
installation!

2. Fix the damper to the wall with the screws. 
Bracket screw hole is 6 mm in diameter.

3. Fill the space between the damper and the 
wall with mortar or gypsum plaster 

(2)

.

*

 Build the support for installation according to 

the drawing, 

see page 9

.

*

 Build a channel support according to the 

drawing, 

see page 13

.

Test the operation of the damper blade!

INSTALLATION

2

7

1

1

2

3

Summary of Contents for FDSD

Page 1: ...r Croatia 385 0 1 33 62 513 info klimaoprema com www klimaoprema com Projektiranje proizvodnja i odr avanje opreme za klimatizaciju ventilaciju i iste prostore Design production and service of Ventila...

Page 2: ...and elastomer rubber Smoke control dampers FDSD are produced in sizes from 200x200 till 1500x800 mm FDSD dampers are equipped with Belimo actuator drives in 24 V or 230 V versions Activation of smoke...

Page 3: ...the dampers blade is acceptable Fire resistance of smoke control damper depends on classification of walls It is allowed to install products to walls only according to products Declaration of Performa...

Page 4: ...steel sheet but on demand can be produced out of Galvanized steel and powder coated Stainless steel EN 1 4301 EN 1 4491 EN 1 4404 AISI 304 316 316L Stainless steel and powder coated EN 1 4301 EN 1 44...

Page 5: ...CATIONS MODULES REPLACEMENTS MAINTENANCE AND OPERATION FDSD DIMENSIONS Length of damper blade outside of casing X H 2 175 mm Actuator A mm C mm D mm E mm BEN M 25 200 90 120 BEE M 25 225 100 120 B 60...

Page 6: ...31 6 33 5 35 5 37 4 39 3 41 3 43 2 45 2 47 2 49 1 51 0 52 9 54 9 56 8 58 7 60 6 62 6 64 5 66 4 Pressure drop tables ZETA VALUES FDSD H B 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950...

Page 7: ...lation opening between the smoke control damper and the wall can be increased by up to 50 of the gap dimension or decreased to the smallest dimension B 80 x H 80 The installation must comply with the...

Page 8: ...ke control ductwork and or may be installed in a fire compartment structure Single compartment smoke control dampers EN 12101 8 Smoke control dampers for use in single compartment areas which may be a...

Page 9: ...n of performance www klimaoprema com fdsd dop Aerated concrete 450 kg m3 or reinforced concrete 2200 kg m3 wall more than 100 mm thick Support for installation with mortar In the smoke control damper...

Page 10: ...r gypsum plaster 1 Recommended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1...

Page 11: ...commended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1 90 Damper blade must...

Page 12: ...ecommended wall opening for the damper installation is B H 80 mm or more up to 50 more Insert damper into wall to the wall limit mark 7 on the damper and bend the fixing bracket 1 90 Damper blade must...

Page 13: ...moke extract duct 8 Dry wall screw staple Rigid wall installation Duct from one side 1 FDSD smoke damper 2 Gypsum mortar mortar 3 Solid wall 4 Promatect L500 50mm strip 5 Promatect L500 50mm strip 6 P...

Page 14: ...l metal duct 1 Smoke damper 2 Flexible connector 3 Sheet steel smoke extract duct In case of fire there is an expansion of the ducts therefore it is necessary to install a flexible connection for conn...

Page 15: ...termosensor Type of Belimo actuator BEN 24 V BEN 230 V BEE 24 V BEE 230 V Torque 15 Nm 15 Nm 25 Nm 25 Nm Nominal voltage power consumption voltage AC DC 24V 50 60 Hz AC 230 V 50 60 Hz AC DC 24V 50 60...

Page 16: ...utton The dampers can be opened and closed via potential free contact or 24 VAC DC external voltage The master can also be controlled via MODBUS TCP IP and RTU or BACnet IP or MS TP and therefore can...

Page 17: ...plate and rectangular shaft 3 Insert new transition plate and rectangular shaft from ERK kit NOTE A Pay attention to the position of the indicator cut B Pay attention to the indicator cut insert the...

Page 18: ...ntact your supplier STORAGE If the damper is not installed immediately Remove any wrapping Protect smoke control damper from dust and contamination Do not expose the smoke control damper to the effect...

Page 19: ...r Croatia 385 0 1 33 62 513 info klimaoprema com www klimaoprema com Projektiranje proizvodnja i odr avanje opreme za klimatizaciju ventilaciju i iste prostore Design production and service of Ventila...

Reviews: