SECTION 4 MODBUS PROTOCOL
Operator/programmer can reach all measured and calculated data via ModeBUS RTU protocol.
Starting address for measured and calculated data is 0.
E.g.:
Three phase average voltage is read via the 0th and 1th registers (16 bits + 16 bits = 32 bit).
PC (or PLC) Request
KLEA Response
Slave ID
01h
Slave ID
01h
Function code
03h
Function code
03h
Register address – high
00h
Byte counts
04h
Register address – low
00h
Register value - high (0)
43h
Number of registers– high
00h
Register value - low (0)
5Dh
Number of registers – low
02h
Register value - high (1)
36h
CRC high
C4h
Register value - low (1)
E0h
CRC low
0Bh
CRC high
68h
CRC low
4Dh
The“Byte counts” information of KLEA response is two times“Number of registers” value of “PC
request” (1 register = 2 bytes).
Register value high(0) and low(0) together with register value high(1) and low(1) constitute a
32-bit value. This value should be converted (typecasted) to a flo t value. The flo t value of the
mentioned 32-bit variable is 221.2143555
Tablo 4-4 Read-only Data
Address Parameter
Description
R/W Unit
Data Type
0
V avg.
Average voltage of three phases
RO
V
32 bit flo t
2
I tot.
Total current of three phases
RO
A
32 bit flo t
4
P tot.
Total active power of three phases
RO
V
32 bit flo t
6
Q tot.
Total reactive power of three phases
RO
VAr
32 bit flo t
8
S tot.
Total apparent power of three phases
RO
VA
32 bit flo t
10
CosØ avg.
Average CosØ of three phases
RO
-
32 bit flo t
12
PF avg.
Average PF of three phases
RO
-
32 bit flo t
14
VLL1
Voltage V1-2
RO
V
32 bit flo t
16
VLL2
Voltage V2-3
RO
V
32 bit flo t
18
VLL3
Voltage V3-1
RO
V
32 bit flo t
20
VLL avg.
Average of line to line voltage of three phases
RO
V
32 bit flo t
22
I nötr
Neutral current
RO
A
32 bit flo t
24
THDV tot.
Total har. distortion of voltage for three
RO
%
32 bit flo t
26
THDI tot.
Total har. distortion of voltage for three
RO
%
32 bit flo t
Summary of Contents for Klea 320P-D
Page 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Page 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Page 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Page 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Page 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Page 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Page 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...