4.5.2 KLEA Setting Parameters
Operator/programmer should use‘10H - Write Multiple Registers and‘06H - Write Single
Register’ to change settings parameters.
Operator/programmer should use ‘0x3H - Read Holding Registers’ function to read setting
parameters.
1 register -> comprises of 2 bytes.
After Klea setting parameters have been changed, in order for the new values to be
saved in non-volatile memory;
0x0000 should be written to register 1998, and
0x0001 should be written in register 1999, within 60 seconds following the last setting change.
Only after that, changes will be stored in the permanent memory.
NOTE1:
3 parameters given with“RO (Read Only)” in
are read-only data. They cannot be
changed by the user. This data is as given below:
• Serial Number
• Firmware Version
• Compiler Version
NOTE2:
1998 addressed variable at the end of
is a “W (only writable)” variable.
Tablo 4-5 Setting Parameters
Address
Parameter
Data Type
Descript.
R/W
Unit
Low Limit
High Limit
Network Settings
2000
Current Transf. Ratio (CTR)
32 bit flo t
-
R/W
-
1
5000
2002
Voltage Transf. Ratio (VTR)
32 bit flo t
-
R/W
-
1
5000
2004
Connection
32 bit flo t
SL1
R/W
-
0
2
2006
Demand Period
32 bit flo t
-
R/W
dakika
1
60
2008
Power Unit
32 bit flo t
SL2
R/W
-
0
1
Energy Settings
2010
T1_1 Start Time
32 bit int.
-
R/W
hour
0
23
2012
T1_2 Start Time
32 bit int.
-
R/W
hour
0
23
2014
T1_3 Start Time
32 bit int.
-
R/W
hour
0
23
Summary of Contents for Klea 320P-D
Page 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Page 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Page 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Page 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Page 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Page 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Page 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...