SECTION 4 MODBUS PROTOCOL
Tablo 4-8 Clear Address Table
Address
Data Type
Parameters/Records to be Cleared
R/W
Value
Modbus func.
1902
32 bit int.
Energy meters
W
1
10H-06H
1904
32 bit int.
Demand values
W
1
10H-06H
1906
32 bit int.
Digital İnput Counters
W
1
10H-06H
1908
32 bit int.
All variables
W
1
10H-06H
1912
32 bit int.
Hourly archieve records
W
1
10H-06H
1914
32 bit int.
Daily archieve records
W
1
10H-06H
1916
32 bit int.
Monthly archieve records
W
1
10H-06H
1918
32 bit int.
Alarm records
W
1
10H-06H
In order to complete to erase/zeroize, programmer should write 1 to the below MODBUS
1898
32 bit int.
Compare erasing zerozing
w
1
10H-06H
Clear me işlemini gerçekleştirmek için:
Clear inecek parametreler ya da kayıtlar ile ilgili adreslere "1" yazıldıktan sonra, 60
saniye içerisinde, 1898 register'ine 0x00 1899 register'ine 0x01 yazılmalıdır.
Summary of Contents for Klea 320P-D
Page 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Page 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Page 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Page 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Page 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Page 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Page 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...