Quadrant
Energy Analyzer
4
Quadrant
Energy Analyzer
SECTION 3 MENUS
When measure is KLEA S tot.=1485000VAr, the result will be as follows,
AO1-GND =[ 10-(-10) x(1485000-(1400x1000)] + (-10) = -5.75V
(1800-1400)x1000
When measure is KLEA V1(L-N)=1695000VA , the result will be as follows,
AO1-GND =[ 10-(-10) x(1695000-(1400x1000)] + (-10) = 4,75V
(1800-1400)x1000
3.2.1.1.6.2 Output 2 Menu
Analog output 2 settings are the same as Output1. Analog output gives output from
AO2- GND pins.
3.2.1.1.6.3 Output 3 Menu
Analog output 3 settings are the same as Output1. Analog output gives output from
AO3- GND pins
3.2.1.1.6.4 Output 4 Menu
Output 4 Menu Settings ve kullanımı, Output 1 Menu ile aynıdır. Analog Output ,
AO4-GND üzerinden alınır.
3.2.1.1.7 Communication Menu
KLEA implements ModeBUS over serial line with RTU mode. In this menu, settings
related with Modebus RTU are accomplished.
V1
V2
V3
V
V
V
A
A
A
I
1
I
2
I
3
1 7 : 2 2
0.0
0.0
220.0
5.0
5.0
5.0
V
1 2 3
I
1
2
1
2
E
Setup
Date / Time
System info
Password
Restart
Default settings
Settings
Measure Meters
Alarms Analysis
Network
Device
Energy
Digital input
Digital output
Communication
Alarm
Clear
Fig. 3-44 Communication Menu
Summary of Contents for Klea 320P-D
Page 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Page 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Page 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Page 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Page 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Page 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Page 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...