Burner : Small
Natural Gas
(1.0kPa)
Universal LPG
(2.75kPa)
Gas Consumption (MJ/h)
4.00
4.00
Injector Size (mm)
0.91
0.56
Burner : Medium
Gas Consumption (MJ/h)
6.70
6.70
Injector Size (mm)
1.18
0.71
Burner : Large
Gas Consumption (MJ/h)
11.50
11.50
Injector Size (mm)
1.59
0.91
Burner : Wok
Gas Consumption (MJ/h)
12.50
13.00
Injector Size (mm)
1.62
0.98
After replacing the nozzles, the installer must check and set the gas pressure and adjust the
burners flame.
Adjust the burner minimum flame height
This adjustment can only be performed by an authorised personnel.
The minimum burner flame is factory adjusted for the gas type stated on the gas type label
adjacent to the gas connection and should not require adjustment. Adjustment may be
required if the nozzles have been replaced or there are special mains pressure conditions.
The operations necessary to perform this operation are the following :
●
Light the burner
●
Turn the knob to the minimum position
●
Take out the knob (and gasket if there is any)
●
Using a suitable sized screwdriver, turn the regulation screw by the side
of the tab shaft until a small regular flame is obtained
●
Put the knob back on and turn it quickly from the maximum position to
the minimum position, checking that the flame does not go off.
●
Make sure the flame is regulated to sufficiently maintain heating of the safety valve
thermocouple.