47 / 82
83000602.Ke
If your chiller is equipped with an internal tank, the further water circulation ensures that residual
air can escape via the tank open to the atmosphere.
For machines without a tank we recommend that an automatic venting valve be installed at the
highest point in the cold water circuit.
6.2.18.
Electrical installation
WARNING! The electrical installation, testing and startup may only be carried
out by qualified personnel. Note and follow the local regulations.
WARNING! Do not switch on the chiller until the hydraulic installation has been
completed and the machine has been filled according to the specifications in
Chapter 6.2.15. Otherwise the machine can be damaged.
The chiller is connected electrically to its main supply terminal in the control cabinet.
(
see Figure 13
Main infeed
)
. A corresponding circuit diagram is enclosed with the unit.
Figure 13: Main infeed
The load cable and fuses must be dimensioned according to the machine's technical specifications
and the regulations of the local power supply company.
The supply cable must be laid in the inside of the machine. Cut-outs for this are provided in the
baseplate. Feed the supply cable, protected by rubber grommets, through these openings (
see
Figure 13 Main infeed)
.
Summary of Contents for vBoxX 10
Page 16: ...16 82 83000602 Ke ...
Page 65: ...65 82 83000602 Ke I Overview of the menu levels Main structure ...
Page 66: ...66 82 83000602 Ke Status ...
Page 67: ...67 82 83000602 Ke Parameters ...
Page 68: ...68 82 83000602 Ke ...
Page 69: ...69 82 83000602 Ke hidden ...
Page 70: ...70 82 83000602 Ke ...
Page 71: ...71 82 83000602 Ke ...
Page 82: ...82 82 83000602 Ke V EC Declaration of Conformity ...