48 / 82
83000602.Ke
Never switch on the chiller immediately if the machine is moved from a cold room to a warm room.
The condensing moisture can damage electronic components. At the initial startup or if starting up
after a lengthy period with no operation, all electronic components must be allowed to acclimatise.
Use an external control cable to set the release (see
Chapter 8.3 External release)
the chiller; this
is laid parallel with the supply cable and is wired to the corresponding terminals in the control
cabinet. On delivery the machine is bridged at the corresponding terminals.
If the electrical installation is completed the phase sequence must be checked. This is done by
checking the rotational direction of the pump. A rotational direction arrow is given on this. If the
rotational direction is not the same the phase sequence can be corrected by swapping two phases
at the main infeed.