73 / 82
83000602.Ke
361
362
Tank press. min Stop
Tank2 press.min Stop
Level in tank is below the
minimum.
Level in the tank is too
low, level sensor dirty,
defective
Fill tank, check the
function of the tank
sensor
373
Press CW-EV max stop
Liquid pressure in the inlet
is too high
Evaporator dirty, water
quantity too high
Clean the evaporator,
adjust the water
quantity, check the
water quality
374
Press CW-EV minstart
Liquid pressure at the
evaporator too low after
switching on.
External gate valve closed,
Filter dirty,
Air in the system.
Open external gate
valve, clean filter, vent
the system.
375
Press CW-EV min run
Cold water pressure at the
evaporator too low during
operation.
External gate valve closed,
Filter dirty,
Air in the system.
Open external gate
valve, clean filter, vent
the system.
381
385
Press. P1 max Stop
Press. P2 max Stop
Liquid outlet pressure too
high
External gate valve closed,
Filter dirty
Open external gate
valve, clean filter,
check overflow valve
setting
383
387
Press. P1 min Start
Press. P2 min Start
Cold water pressure at the
pump outlet too low after
switching on.
Flow rate too high,
Air in the system.
external pressure loss too
low
Pump is operating outside
the set limits
external pipe system not
yet filled
Fill and vent
Increase external
pressure loss
384
388
Press P1 min run
Press P2 min run
Cold water pressure at the
pump outlet too low during
operation.
Flow rate too high,
Air in the system.
external pressure loss too
low
Pump is operating outside
the set limits
Increase external
pressure loss
501
AI Temp.inlet
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
502
AI Temp.Outlet 1
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
503
AI Temp.Outlet 2
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
511
AI press cw-evaporat
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
513
AI press pump 1
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
514
AI press pump 2
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
515
AI press tank 1
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
516
AI press tank 2
Output value of the sensor
is incorrect
Sensor short-circuit or
sensor break
Use the characteristic
curve to check the
electrical connection of
the sensor
Summary of Contents for vBoxX 10
Page 16: ...16 82 83000602 Ke ...
Page 65: ...65 82 83000602 Ke I Overview of the menu levels Main structure ...
Page 66: ...66 82 83000602 Ke Status ...
Page 67: ...67 82 83000602 Ke Parameters ...
Page 68: ...68 82 83000602 Ke ...
Page 69: ...69 82 83000602 Ke hidden ...
Page 70: ...70 82 83000602 Ke ...
Page 71: ...71 82 83000602 Ke ...
Page 82: ...82 82 83000602 Ke V EC Declaration of Conformity ...