Understanding the Error Codes
Error codes will be shown on the display when either an internal fault such as
high internal
temperature
or external fault like AC
input voltage out of range
is detected. The unit will shut down.
Code
Condition
Corrective Action
A01
Temperature Sensor (BTS) is defective.
Check and or replace the sensor.
E01
Unit shutdown due to low AC Input (< 85 +/- 5Vac)
Check AC input source. The unit will automatically
recover when the AC Input voltage return to
> 108 +/-5Vac
E02
Unit shutdown due to high AC Input (>270 +/- 5Vac)
Check AC input source. The unit will automatically
recover when the AC Input voltage returns to
< 260 +/-5Vac
E03
Battery is connected backwards
Check all battery connections
E04
Charger Internal temperature is too high and it has
shutdown. The unit will automatically recover when
the unit cools down.
The ventilation of the unit is blocked or the environmental
temperature is high. Reduce charging current or improve
the ventilation near the unit.
E05
Not used.
E06
For non- Lithium Battery type setting:
High battery temperature >70 °C (158°F) is sensed
by the BTS when installed. The unit will shut down.
The unit will automatically recover when the battery
temperature has reduced to 60°C (140°F).
For Lithium battery type setting:
High battery temperature >60 °C (140°F) is sensed
by the BTS when installed. The unit will shut down.
The unit will automatically recover when the battery
temperature has reduced to 55°C (131°F).
Check the battery, charger setting, and its environment.
E07
For non- Lithium Battery type setting:
Low battery temperature < -25°C (-13°F) is sensed
by the BTS when installed. The unit will shut down.
The unit will automatically recover when battery
temperature reaches
-20°C (-4°F).
For Lithium Battery type setting:
Low battery temperature < 0°C (32°F) is sensed by
the BTS when installed. The unit will shut down. The
unit will automatically recover when battery
temperature reaches 5°C (41°F).
It is not recommended to charge the battery at low
temperatures.
E08
DC Output fuses are blown.
Check battery connection and replace the fuse with the
same type and rating.
E09
Unit shutdown due to high battery voltage (> 17 Vdc
on 12V model and >34 Vdc on 24V model). The unit
will automatically recover when battery Voltage is
reduced to <16Vdc on 12V model or <32 Vdc on 24V
model.
Check battery and charger settings. Check also if there is
any other DC supply connected to the battery banks.