Understanding the Error Codes 

Error  codes  will  be  shown  on  the  display  when  either  an  internal  fault  such  as 

high  internal 

temperature

 or external fault like AC 

input voltage out of range

 is detected. The unit will shut down. 

Code 

Condition 

Corrective Action 

A01 

Temperature Sensor (BTS) is defective. 

Check and or replace the sensor. 

E01 

Unit shutdown due to low AC Input (< 85 +/- 5Vac) 

Check AC input source. The unit will automatically 
recover when the AC Input voltage return to  
> 108 +/-5Vac 

E02 

Unit shutdown due to high AC Input (>270 +/- 5Vac) 

Check AC input source. The unit will automatically 
recover when the AC Input voltage returns to  
< 260 +/-5Vac 

E03 

Battery is connected backwards 

Check all battery connections 

E04 

Charger Internal temperature is too high and it has 
shutdown. The unit will automatically recover when 
the unit cools down. 

The ventilation of the unit is blocked or the environmental 
temperature is high. Reduce charging current or improve 
the ventilation near the unit. 

E05 

Not used. 

 

E06 

For non- Lithium Battery type setting: 

High battery temperature >70 °C (158°F) is sensed 
by the BTS when installed. The unit will shut down. 
The unit will automatically recover when the battery 
temperature has reduced to 60°C (140°F).  

For Lithium battery type setting: 

High battery temperature >60 °C (140°F) is sensed 
by the BTS when installed. The unit will shut down. 
The unit will automatically recover when the battery 
temperature has reduced to 55°C (131°F).  

Check the battery, charger setting, and its environment. 

E07 

For non- Lithium Battery type setting: 

Low battery temperature < -25°C (-13°F) is sensed 
by the BTS when installed. The unit will shut down. 
The unit will automatically recover when battery 
temperature reaches  
-20°C (-4°F). 

For Lithium Battery type setting: 

Low battery temperature < 0°C (32°F) is sensed by 
the BTS when installed. The unit will shut down. The 
unit will automatically recover when battery 
temperature reaches 5°C (41°F). 

It is not recommended to charge the battery at low 
temperatures. 

E08 

DC Output fuses are blown. 

Check battery connection and replace the fuse with the 
same type and rating. 

E09 

Unit shutdown due to high battery voltage (> 17 Vdc 
on 12V model and >34 Vdc on 24V model). The unit 
will automatically recover when battery Voltage is 
reduced to <16Vdc on 12V model or <32 Vdc on 24V 
model. 

Check battery and charger settings. Check also if there is 
any other DC supply connected to the battery banks.  

 

 

Summary of Contents for Abso Charger 12V 100A

Page 1: ...Abso Charger 12V 100A AC12100 24V 50A AC2450 Owner s Manual...

Page 2: ...Page 2...

Page 3: ...Abso Charger Misuse may result in damage to the unit and or cause harm or serious injury Product Numbers AC12100 Abso Charger 12V 100A AC2450 Abso Charger 24V 50A Document Part Number MU AC12100 Rev...

Page 4: ...STALLING THE CHARGER 10 5 UNIT OPERATION 13 6 SPECIFICATIONS 19 7 WARRANTY 20 Appendix A1 GEL Flooded AGM Setting CH1 CH2 CH3 Appendix A2 1 Lithium Setting CH1 Appendix A2 2 Lithium Setting CH2 3 Appe...

Page 5: ...an explosion WARNING Explosion hazard Do not use the unit in the vicinity of flammable fumes or gasses such as propane tanks or large engines Avoid covering the ventilation openings Always operate th...

Page 6: ...ere is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning...

Page 7: ...lgorithm During normal operation the charger will do a full charge cycle to float stage on Battery Bank 1 Once the float stage is reached the charger starts charging Battery Banks 2 and 3 together wit...

Page 8: ...Battery Bank 3 Chassis Ground The unit chassis has to be grounded properly to the common ground point on the system Digital Remote optional The Display Remote Part Number ACRM1202 sold separately is...

Page 9: ...e battery voltage reaches approximately 13 5V This timer is set to avoid battery overcharging The charger will override the Absorption to Float stage condition and goes to Float stage when it times ou...

Page 10: ...he mounting template on the right to mark the positions of the mounting screws Drill the 4 mounting holes and place the Charger in position and fasten the unit to the mounting surface See mounting loc...

Page 11: ...screws located at the top of the AC compartment cover Remove the top section of the AC Input wire strain relief located at the bottom of the base panel inside the AC wiring compartment by unscrewing t...

Page 12: ...s Remote Port to the COM_2 port on the Remote Display Panel The Remote Display Panel is now ready to use Both charger displays will show CON indicating the chargers are connected in parallel And all...

Page 13: ...display will then show the next menu to continue with other setting parameters NEXT Press the hold the key for longer than 5 seconds to RESET the charger Display will show RST and it will force the ch...

Page 14: ...27 V 0 54V AGM 0 21 V 0 42V For use when Battery Temperature Sensor is in use No setting on the unit is required and the unit will automatically sense the Battery Temperature Sensor when it is connec...

Page 15: ...rent L current in A Charging stages CH1 only Mode 2 Bulk and Absorption stage only Mode 3 Bulk Absorption and Float stage Battery temperature CH1 only Low Lo Normal nor High hi For Lithium battery typ...

Page 16: ...ed channel first and follows with 1 hour of 15 5V equalization process Consult or follow the instruction as provided by the battery manufacturer on how to check the battery electrolyte level and or re...

Page 17: ...g code will display The charger will recover automatically back to the maximum charging current when the environmental temperature drops to below 45 C Over Temperature Shutdown When the charger senses...

Page 18: ...alled The unit will shut down The unit will automatically recover when the battery temperature has reduced to 60 C 140 F For Lithium battery type setting High battery temperature 60 C 140 F is sensed...

Page 19: ...ith back lighting Charging status Battery Voltage Warning and Fault Code A01 E01 09 AC Input and DC Output Connection AC Input Connection Hardwire or AC with EU UK AZ plug DC Output Connection POS Hea...

Page 20: ...ive if products are deemed non working or malfunctioning the product may be returned to the purchasing store within 30 days of original purchase Any defective unit that is returned to the manufacturer...

Page 21: ...Page 21...

Page 22: ...Page 22...

Page 23: ...Page 23...

Page 24: ...Page 24...

Page 25: ...Page 25...

Page 26: ...Page 26 Appendix B...

Reviews: