3.2.4. Inspection for the welder and generator set

Before starting the set, be sure that the air switch should be turned to  OFF  state. 

If the switch is not turned to  OFF  state, when starting the diesel engine, 

suddenly loading is very dangerous.

The generator should be grounded to prevent the electric shock.

Blow the dust out of the generator control box inside and surface by using dry 

compressed air(air pressure should be less than 1.96 x 105 Pa) or manual. 

Check the clean condition on the slide rings, check the carbon brush pressure, 

check whether the position on the slide rings are correctly fitted. Check whether 

the fixing is reliable and whether the contact is good.

According to the electric wiring diagram, check whether the wiring lines are 

correct and whether the connection joints are firm.

Use a 500V megameter to measure the insulation resistance of the electric 

device section and the resistance should be not less than 2 megohms. Otherwise 

it is necessary to carry out a dry treatment. While measuring, AVR should be 

disconnected. Otherwise AVR may be burned out. (For the noise quieting type set, 

it is possible not to carry out this check.)

3.2.5. Before delivering the diesel engine from the factory, the fuel oil and 

the machinery oil had been discharged.

Before filling the fuel oil and starting the diesel engine, it is necessary to check 

whether there is any air mixed into the oil circuit. If there is any, the air should be 

discharged. The concrete method is to unfasten the connecting nut between the 

oil injection pump and the oil transmission pipe so as to discharge the air in the 

fuel oil until there is no air bubbles to be appeared. Then fasten the connecting 

nut again.

Potentiometer

Electric Lock

DC Output Receptacle

Anode Wiring Terminal

Cathode Wiring Terminal

Grounding Terminal

Knob Switch

Automatic Air Switch

Voltmeter

Operation
Director Light

-

-

3.3  Inspection and Operation of the Diesel Engine

3.3.1  Low oil pressure alarm system/braking device

 

Our diesel engine possesses the low oil pressure alarm system/braking device. 

When the oil pressure goes down, the device will automatically brake the diesel 

engine to avoid the blocking-up of the diesel engine because the oil pressure is 

too low and the lubrication is insufficient. (2 GF-L can not stop the machine 

automatically.)

If the diesel engine is running under the condition that the lubrication oil is 

insufficient, the oil temperature will go up too high. On the other hand, it is also 

dangerous if these is too much oil. Because the machinery oil may be burned, 

this will make that the revolution speed of the engine increase suddenly and 

results in  abnormal fast running . For this purpose, it is necessary to check the 

machinery oil and the oil level should reach the stipulated height.

3.3.2  How to open the machinery casing door and the housing (TW series 

set)

(1) Open the machinery casing door, 

rotate the handle counterclockwise. Lift 

the door and carry out the daily check.

(2) Unfasten the bolts of the air filter 

housing and take out the oil nozzle 

housing to check the air filter.

3.3.3  Trial run operation

When your diesel engine is a new set, a large loading will reduce the engine's 

life. Within the first 20 hours, it is necessary to carry out the trial run.

Handle

-

-

Summary of Contents for KDE180EW

Page 1: ...AIR COOLED DIESEL WELDER AND GENERATOR SET KDE180XW KDE180EW KDE180TW...

Page 2: ......

Page 3: ...erator Set 3 6 How to operate the Welder and Generator Set 3 7 Loading 3 8 Breaking the Welder and Generator Set 3 9 KDE180 Set 4 Maintenance of the Welder and Generator Set 4 1 Regular Maintenance 4...

Page 4: ...tion oil Start battery Combustion oil tank volume L Low oil pressure stop protection system Cylinder diameter Stroke mm Continuous operation for 10 hours Three phase IGBT PWM Transmission shaft rigid...

Page 5: ...sy Capacitor Welding output terminal post assembly No Parts No Description Qty 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 QF1 V HL X1 X2 SA DT FU1 Z1 Z2 W1 W2 W3 W4 W5...

Page 6: ...sonal accidents and the equipment damages may be caused 3 1 1 Fire prevention The combustion oil used in the diesel engine is light diesel oil The gasoline kerosene and other oils should not be used U...

Page 7: ...tion NOTE Potentiometer Electric Lock Wiring Terminal AC Output Receptacle Grounding Terminal Automatic Air Switch Fuse 8 a b 3 2 Preparation before the Start 3 2 1 Select and treat with combustion oi...

Page 8: ...t About one month or 20 hours Interval of 3 months or 100 hours Time for changing the oil Top Limit Lower Limit Although there are the low oil pressure alarm system the stop device At the time of star...

Page 9: ...ion pump and the oil transmission pipe so as to discharge the air in the fuel oil until there is no air bubbles to be appeared Then fasten the connecting nut again Potentiometer Electric Lock DC Outpu...

Page 10: ...relieve the switch handle Let the switch restore to ON position automatically 5 If the diesel engine doesn t start after 10 seconds please wait for anther 15 seconds and make the start again If the st...

Page 11: ...ark add some distilled water to make that the liquid level goes up to a higher mark If the electrolyte in the battery is too less the diesel engine will not start Because the electric power is insuffi...

Page 12: ...op immediately It is necessary to check the oil height and add some oil 3 Do not unfasten the adjustment bolt used for adjusting the speed limit of the diesel engine or do not unfasten the high pressu...

Page 13: ...the switching board By adjusting to a suitable position the welding can be carried out If a smaller current is needed it is possible to reduce the not be used for a long time The position for the rate...

Page 14: ...used only for the welding separately the welding cable should be removed or protected When the set is used only for the welding separately the air switch should be turned off or the power supply plug...

Page 15: ...justvalveclearanceforintakeandexhaustvalves Check commutator brush and slip ring Every year or 1000 Hrs Daily check First month of 20 Hrs Every 3 months or 100 Hrs Every 6 month or 500 Hrs 1st time 2n...

Page 16: ...ator clock whether they are in good condition If spark occurs they have to be adjusted properly Every 3 months or 100 hours Clean time monthly Battery fluid check 4 1 1 Changing engine oil Every 100Hr...

Page 17: ...f you have any question or problem when you meet in your operation please contact with our company or our dealer and tell the following information 1 The type of diesel generator sets the No and type...

Page 18: ...the cable will be burnt If the cable is long and thin the input voltage of the electric appliance will be not enough causing that the generator doesn t start In the following formula you can calculate...

Page 19: ...t is C 0 03 When the relative humidity is 100 the modified coefficient is C 0 04 Counting example When the rated power of generator is P 5KW altitude is 1000m ambient N temperature is 35 relative humi...