26
(1)Negative terminal (-) (2) AC terminal (~)
(3) AC terminal (~) (4)Negative terminal (+)
6.8
Charging Regulator
Loosen the positive battery cable when starting the engine and connect a DC current meter between the
positive cable and positive terminal. The indicated current cannot exceed 1.5A. If there is no current
present, replace the regulator
DC charging
voltage
13~14V
DC charging
current
<
1.5A
AC Input (blue)
Shell grounding Output positive pole (red)
6.9 Timing relay
Put the ignition switch on the “OFF” position, connect a voltmeter to the white and yellow/green wires.
Place the ignition switch in
the “ON” position, hold on for 7 seconds and then place in the “OFF” position.
A reading of 12V should be present for 7~12 seconds then the output should drop to 0 volts.
Yellow Green White
Red Blue
Black Black