General Vent Installation Information
This gas appliance is approved to be vented either through the side wall or vertically through the roof. Only Kingsman Flex (Z-
Flex) venting kits and components specifically approved and LABELED for this stove may be used.
Model
MQRB5143
is approved for use with DuraVent- DirectVent Pro Direct Vent system (Model DV-GS Series), and
AmeriVent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp. Not available for
MQRB6961.
DuraVent- DirectVent Pro, AmeriVent, and Selkirk Direct Temp
When using DuraVent- DirectVent Pro, AmeriVent pipe, ICC Excel Direct, Metal Fab Sure-Seal DV, or Selkirk Direct Temp a
Dura-vent adapter must be used (part # Z57DFA). Follow installation instructions provided by the appropriate manufacturer for
installation of pipe, and adhere to the clearance to combustibles provided in this manual. Apply a bead of Mill Pac high temp
sealant to all joints of pipes, adapters and termination as recommended.
1. Remove the two [2] Standoffs at the
vented end of the Fireplace.
2. Apply RTV Red Silicone to the
underside of the Adapter Plate around
the perimeter of the screw holes.
3. Fasten Adapter Plate to the top of the
unit using the supplied DT Screws.
4. Replace the Standoffs.
Flex Pipe Venting
Flex pipe is shipped in an unexpanded length. Therefore, when installing the pipe, expand it completely and then cut off the
remaining length. A flex pipe can be expanded to twice their shipped length (e.g. 4ft. to 8ft).
Do not use more than 2 couplers to extend short pipes. Single sections are preferred in an installation attaching at the
fireplace and termination.
Place the spring spacers provided approximately every two feet to stabilize inner flex in the center of the outer flex pipe. When
forming bends place spring in bend or before and after.
ONLY VENTING COMPONENTS SPECIFICALLY APPROVED AND LABELED FOR THIS FIREPLACE MAY BE USED.
Termination
It is imperative that the vent termination be located observing the minimum clearances as shown. There must not be any
obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination plate.
Do not locate termination where excessive snow or ice build-up may occur. Be sure to check vent termination area after snow
falls and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed
towards vent termination area.
Venting terminal shall not be recessed into a wall or siding.
WARNING: DO NOT mix parts from different systems unless stated in the manual.
Kingsman Flex venting MUST be used on the MQRB4436 and MQRB6961.
Use of DuraVent- DirectVent Pro or other hard pipe Venting systems is not permitted.
Contents: 1 ea. 8” Adapter Plate
6ea. DT Screws
Eight Inch Hard Pipe Adapter (Z57DFA) for MQRB5143 Only
94