MQRB6961 Single Sided Framing
An
MQRB6961BK
Kit is required for a Single Sided Installation.
Before you begin Framing
- Determine whether the
Wall Surface
will be flush with the face of the fireplace (Fireplace
and wall to be covered with Non-Combustibles, such as tile), or the
Framing
will be flush
with the face of the fireplace (Flat Wall appearance).
Note:
If using optional surround, maximum thickness for non-combustible material is 3/4”.
(Continued)
*21” Min.
Dimension is for
Wall
Surface Flush
with
fireplace.
Add 1/2” to this
Dimension where a
non-combustible wall
surface will cover the
unit (see
Nailing Tab
Guide
page also).
21” Min.*
FRAMED OPENING 71-1/2” X 45-1/2”
CANTILEVER FINISHED MINIMUM OPENING IS 77-1/2” WIDE
Framing Style shown is for illustration purposes only.
This structure is NOT load bearing.
Steel Stud Framing Shown
Fireplace vent MUST maintain min. 1” clearance from combustible (Wood) framing.
However, if steel stud framing is used, 1” vent clearance is not required.
Also refer to these sections:
Clearance to Combustibles
Enclosure Heights
Venting
Note:
If Combustible (Wood) Framing
Studs are used, they must be Rotated to
allow Min.1” Clearance from Airbox.
1” Min Clearance Around All Sides of Airbox
39