Compact Commercial Softener Owner
’s Manual
14
A prefilter MUST be used before a softener to prevent any foreign material from getting
into the equipment.
VERY IMPORTANT!
Where a brine drum overflow could cause damage, a 1/2" I.D.
overflow line MUST be installed on drum and connected to a drain. Make sure the drain
or overflow line is not higher than brine fitting.
NOTE:
Clear area along wall where PVC drain line will be run to floor drain.
KineticoPRO does not recommend running flexible tubing across floor or
along walls, as it may be kicked out of discharge point at floor drain, or line
may become pinched resulting in improper backwashing.
When installing a plastic component in line, it is recommended that grounding straps be
put in place BEFORE the lines are actually cut to ensure that the ground is never broken.
When installation is complete, plumbing lines MUST be chlorinated for sanitation.
Common household bleach may be used. The amount of bleach will vary on plumbing
size, lengths, and fixtures.
NOTE:
A clean grade of salt is strongly recommended. DO NOT use rock salt.
This unit will NOT make potable water from a non-potable source.
Read all steps, guides and rules carefully before installing and using the
KineticoPRO Softener.
KineticoPRO CC Series Softener Installation
1.
Determine location to install equipment. Make sure that the unit will be on a flat surface. Test water to
confirm unit is properly sized for installation. If sand/silt or turbidity is present, a separate prefilter should
be installed.
A ladder should be used for all work overhead that would be beyond your natural reach. If
working continuously at a height of six feet or more, the appropriate safety devices must be
employed.
2.
Install with by-pass valving. Note the inlet and outlet arrows on valve head.
3.
For Hot Water Applications, the addition of a mixing valve, thermometer and check valve are recommended.
This will prevent overheating of the softener during off periods or during initial daily start-up.
▪
Position mixing valve on hot/cold line, prior to softener.
▪
Position thermometer after mixing valve.
▪
Position check valve after softener, but before hot water appliance (such as a commercial dish
machine).
By-pass Valving
Inlet
Outlet
Drain
Overflow