Sirius Capacitor Module
–
User Manual
Model Number - 3550-48-B-1.7C-M-SD-A-L-19G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
29
7
Connecting the Module in Parallel:
Any number of Modules can be connected in parallel.
•
Steps to Connect Modules in Parallel:
Refer to the parallel combination of the Sirius Modules as shown below and make your connection
accordingly.
•
Connect the
positive (+)
of the
F12 Terminal
of all Modules.
•
Connect the
negative (-)
of the
F12 Terminal
of all Modules.
•
Take out the output positive and output negative from the respective common point.
Caution!
Do not use more than 10A to recover the Module.
Note!
Switch ON only the Circuit breaker when connecting in Parallel.
Caution!
Charge all the Modules to 100% SOC or same voltage level before
connecting them in Parallel.
Note!
Series connection of Modules is NOT allowed.