![Kilowatt Labs 7100-48-B-2C-TM-SD-A-G User Manual Download Page 23](http://html1.mh-extra.com/html/kilowatt-labs/7100-48-b-2c-tm-sd-a-g/7100-48-b-2c-tm-sd-a-g_user-manual_1967119023.webp)
Sirius Capacitor Module
–
User Manual
Model Number -7100-48-B-2C-TM-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
23
•
Take the Output
Negative from
first
Module and Output Positive from the
last
Module.
Caution!
Charge all the Modules to 100% SOC or same voltage level before
connecting them in Series.
Note!
Switch ON the bypass Circuit breaker when connecting in Series, otherwise
it will damage the electronic switch.
Note!
Modules cannot be connected in series-parallel combination under any
circumstance.
Caution!
The Bypass circuit breaker is not protected with electronic switch, therefore
during over-voltage, under voltage and high temperature conditions, the
terminal will not shutdown. It only gives protection for over current
condition.