Device
Setting
Under 40A
Charger
40-60A
Charger
60-150A
Charger
Inverter
Charger
Absorb Time (some
controllers do not al-
low a selection under
6 minutes, please
contact KiloVault for
additional information)
Under 6 minutes
Under 4 minutes
Under2 minutes
Battery Capacity
150 Ah (7.5 kW) per KiloVault® HAB™
Battery Type
Lithium Ion or Custom - whichever provides access to the re-
quired settings
Absorption
56V
Bulk (98% to 100% of
Absorption)
56V
Bulk Current
75 A
Charge Cycle
2 Stage No Float
HBCO (High Battery
Cut Out)
57 V (58V for Schneider Equipment)
LBCO (Low Battery
Cut Out)
48.2 V (48V for Schneider Equipment)
LBCO Delay
3 seconds
LBCO Hysteresis
2 V
Max Bulk Current
Set to whatever percentage of the inverter current plus the
charge controller current is less than or equal to 100 A
Absolute Maximum
Charge Rate
120A per HAB™ in Parallel (Solar Charge Controller Amps +
Percentage of Inverter/Charger Max DC Output.
Example: For a single HAB™ system with an inverter/charger
maximum DC output of 100 A and a solar charge controller
capable of 80 A, you would limit the inverter/charger output to 40
A (so the total is 120 A).
Recharge / Re-Bulk
Volts (80% DoD)
51.4 V (used to set voltage that triggers charge start)