This manual
is f
or
use b
y qualified personnel
onl
y
Figure 11: HAB™ Access Ports
JUNE 2022 / Rev: 1.0
Protective (grounding) conductor terminal
WARNING
UNGROUNDED EQUIPMENT
Equipment ground terminals must be reliably connected to ground by appropriately sized
grounding conductors. All installations must comply with national and local codes. Consult
local and national codes for specific grounding and bonding requirements.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The
KiloVault® HAB™
is provided with ground terminals that must be reliably connected to
ground (protective earth) by appropriately sized equipment grounding conductors. System
grounding for the AC and DC systems must be done according to all applicable NEC and local
installation codes. To connect the
HAB™
to the DC grounding system, use the ground lug at
the bottom of the chassis (see Figure below). The terminal accepts
wires from #14 AWG (1.63 mm) to #2AWG (6.54 mm).
System grounding for the DC system, which typically involves
Note:
If a grounded DC system is required, ensure that the system bonding is done in
one location only, and that all conductors and connections comply with all applicable
NEC and local installation codes.
24