18
PWR Series Setup Guide
Connecting the Load (Cont.)
Connection to the Output Terminal on the Front Panel
The specifications of the PWR are defined for output terminal on the
rear panel. Those on the front panel may not satisfy the specifica-
tions.
Like the output terminal on the rear panel, the chassis terminal is
normally connected to either the - (neg.) or + (pos.) output terminal.
WARNING
• Possible electric shock. Be sure to turn the POWER
switch off before touching the output terminal on the
front panel.
Do not use the terminal with the front output terminal
cover removed. In addition, be sure to attach the OUT-
PUT terminal cover on the rear panel.
•
Possible overheating or fire. Do not supply currents
that exceed 30 A from the output terminal on the front
panel on the L type.
If the front output terminal cover is damaged or lost, contact Kiku-
sui distributor/agent.
[P1-000-408]
M6
Attach so that the wire passes
through this section.
Crimping terminal
Knob
1
Turn the POWER switch off.
2
Attach crimping terminals to the load wires.
3
Remove the knob and connect the load wire to the out-
put terminal on the front panel.
4
Attach the knob.