![Kieback & Peter MD10-FTL-HE Quick Start Manual Download Page 37](http://html1.mh-extra.com/html/kieback-and-peter/md10-ftl-he/md10-ftl-he_quick-start-manual_1966428037.webp)
37
/44
Messages
|
en:key
»
Malfunctions
Transmission function
The room sensor continuously monitors the wireless radio connections. If a transmission
malfunction is detected in the room sensor, “Code
Δ
8” appears.
►
1
Reset the room sensor to its defaults.
“Code
Δ
8” disappears
→
Restoring the defaults (S.28)
2
Register the valve controllers again.
→
Registering the valve controller (S.14)
System time
The room sensor continuously monitors system time. If a time or date malfunction is
detected in the room sensor, “Code
Δ
3” appears.
►
1
Reset the time and date.
“Code
Δ
3” disappears
→
Changing the time and date (S.25)
Icon
State
Explanation
Antenna
Code
Δ
8
Off
On
Transmission function malfunctioning
Room sensor
Code
Δ
3
On
System time malfunctioning
Room sensor
If the room sensor transmission function is continuously malfunctioning, the
valve controllers operate in comfort mode. There is no reduction to economy
mode.