en:key
|
Commissioning
18
/44
5a
Screws:
Drill two mounting holes in the marked positions.
6a
If necessary, insert wall plugs into the mounting holes.
7a
Hold the wall mount against the wall in the marked position and screw the wall
mount in place tightly, making sure that it is aligned correctly.
Go to item 8.
5b
Bonding:
Remove a protective film from the adhesive pad and stick it to the
smooth side of the wall mount.
6b
Remove the second protective film from the adhesive pad and press the wall
mount onto the marked position on the wall, making sure it is aligned correctly.
7b
Press the “wall mount” onto the surface repeatedly and firmly.
The pressing force is more important than the duration.
8
Check the “wall mount” is mounted and aligned correctly on the wall.
9
Mark the room sensor and the wall mount with a unique number using the
enclosed adhesive numbers.
10
Place the room sensor on the wall mount.
11
Slide the room sensor down up to the stop.
The “holding bar” on the “wall mount” clicks audibly into place.
»
Mounting the valve controller
The valve controller is fastened directly onto radiator valves with an M30x1.5 DIN 13
connection (e.g. Heimeier, Honeywell, Cazzaniga, Oventrop - 1998 or later).
If several room sensors are removed from their rooms, identifying them with
a number makes it easier to find the correct room. The valve controller does
not need to be re-registered then.