Commissioning
|
en:key
You want to switch on the room sensor and test an installation location for it.
►
1
Press the “occupancy button” and the “setting button” simultaneously and
hold them down for 5 seconds.
“rEs” is displayed briefly.
The “Code
Δ
,” “Sun,” “Occupancy” and temperature icons appear.
The room sensor is switched on; the occupancy sensor and solar cell are
active.
2
Position the room sensor at the potential installation location.
3
Check the “Sun” icon.
4
Move around the room and check the “Occupancy” icon.
If the installation location is good, the room sensor can be mounted there.
If the installation location is bad, the test must be repeated in another location.
Evaluation
Display
Installation location
good
The “Sun” icon is displayed permanently, and the “Occu-
pancy” icon switches from “Person inside the house” to
“Person outside the house” and back again
Installation location bad
The “Sun” icon is not displayed or ...
The “Occupancy” icon does not switch to “Person inside the
house” and remains unchanged.
If the room sensor switches off after 15 minutes, switch it back on again.