Kieback & Peter MD10-FTL-HE Quick Start Manual Download Page 13

13

/44

Commissioning

 

|

 

en:key

You want to switch on the room sensor and test an installation location for it.

1

Press the “occupancy button” and the “setting button” simultaneously and 
hold them down for 5 seconds. 

“rEs” is displayed briefly.  
The “Code 

Δ

,” “Sun,” “Occupancy” and temperature icons appear. 

The room sensor is switched on; the occupancy sensor and solar cell are 
active.

2

Position the room sensor at the potential installation location.

3

Check the “Sun” icon.

4

Move around the room and check the “Occupancy” icon.

If the installation location is good, the room sensor can be mounted there.  
If the installation location is bad, the test must be repeated in another location.

Evaluation

Display

Installation location 
good

The “Sun” icon is displayed permanently, and the “Occu-
pancy” icon switches from “Person inside the house” to  
“Person outside the house” and back again

Installation location bad

The “Sun” icon is not displayed or ...

The “Occupancy” icon does not switch to “Person inside the 
house” and remains unchanged.

If the room sensor switches off after 15 minutes, switch it back on again.

Summary of Contents for MD10-FTL-HE

Page 1: ...A Quick Start Guide Room Sensor Valve Controller...

Page 2: ......

Page 3: ...ng the valve controller 14 Mounting the room sensor 16 Mounting the valve controller 18 Operation Setting the comfort temperature 21 Changing to comfort mode economy mode 22 Start change end vacation...

Page 4: ...guide use other documents or contact an authorized service technician Other documents can be downloaded from the website www enkey de or directly via the QR code Other documents Quick start guide bri...

Page 5: ...t guide is an integral part of the devices and must be kept eas ily accessible at all times If the devices are not used according to the instructions in this quick start guide the existing protective...

Page 6: ...sensors with EnOcean technology are significantly lower than those from equivalent conventional light switches Other devices such as wireless telephones are higher than those of wireless radio switche...

Page 7: ...components Item Designation Explanation 01 Rotary knob Adjusts comfort temperature Setting the comfort temperature S 21 02 Octagon nut Fastens the valve controller to the valve Mounting the valve con...

Page 8: ...ows information on the current state of the room sensor and valve controller 02 Occupancy sensor Detects presence absence for the heating time profile 03 Solar cell Generates energy for the room senso...

Page 9: ...the room sensor S 16 07 Holding bar Holds the room sensor in place on the wall mount 08 Setting button Switches room temperature on with occupancy button Starts registration procedure Resets room cont...

Page 10: ...2 Battery Energy storage unit system status System status S 36 03 Windows Rapid temperature drop detected System status S 36 04 Code Status messages System status S 36 Malfunctions S 37 05 Prog Valve...

Page 11: ...ation location S 12 System status S 36 09 Occupancy Occupancy sensor is active test installation location Detected presence absence Vacation mode is active Testing the installation location S 12 Chang...

Page 12: ...nt the room sensor at a height of approx 1 50 m above ground level Item Designation Explanation 01 Occupancy sensor Detects presence absence for the heating time profile 02 Solar cell Generates energy...

Page 13: ...heck the Sun icon 4 Move around the room and check the Occupancy icon If the installation location is good the room sensor can be mounted there If the installation location is bad the test must be rep...

Page 14: ...on procedure has been com pleted In such cases all the valve controllers must be registered in a new procedure Item Designation Explanation 01 Antenna Wireless connection system status 02 Prog Valve c...

Page 15: ...The valve controller acknowledges startup with one signal tone shortly afterwards The valve controller acknowledges successful registration with two signal tones Room sensor shows the number of regist...

Page 16: ...or if Code 2 appears on the display the registration was not successful and must be repeated Up to 10 minutes may elapse before the first data exchange If the room sen sor switches off after 15 minute...

Page 17: ...ll mount to even surfaces 02 Fastening material Select based on surface Not included in scope of delivery 03 Adhesive digits Identifies room sensor and wall mount 04 Holding bar Holds the room sensor...

Page 18: ...l mount onto the surface repeatedly and firmly The pressing force is more important than the duration 8 Check the wall mount is mounted and aligned correctly on the wall 9 Mark the room sensor and the...

Page 19: ...valve 03 Rotary knob Adjusts comfort temperature 04 Flange Connection to the radiator valve Do not attach the flange and the octagon nut to the radiator valve in a tilted position If they are attached...

Page 20: ...alve 2 Turn the rotary knob on the valve controller to the maximum setting 3 Ensure that the valve controller is not tilted when mounted on the radiator valve 4 Tighten the octagon nut on the radiator...

Page 21: ...pends on the radi ator and the size of the room In exceptional cases settings on the heating system or insufficient radiator size can result in the set comfort temperature not being reached Item Desig...

Page 22: ...g the comfort temperature It is too warm for you and you want to lower the comfort temperature 1 Turn the rotary knob to a lower setting The room temperature drops to the set comfort temperature Chang...

Page 23: ...then the learned heating time profile reactivates and the Auto icon appears Changing to economy mode You want to change to economy mode 1 Briefly press the occupancy button The Occupancy icon changes...

Page 24: ...n start displays appear alternately Item Designation Explanation 01 Occupancy but ton Start change vacation mode 02 Vacation Start display of vacation mode 03 Duration Current duration of vacation mod...

Page 25: ...Vacation mode activated Comfort mode economy mode changes to vacation mode after 00 00 You want to deactivate vacation mode immediately 1 Set the Duration display to 00 The time or current room temper...

Page 26: ...e month display flashes after approx 3 seconds current minute Item Designation Explanation 01 Occupancy but ton Change enter time and date 02 Time date Start display of time and date 03 Hour day Displ...

Page 27: ...button just once to confirm the displayed month or multiple times until the current month appears The Hour day display flashes after approx 3 seconds current day 7 Briefly press the occupancy button t...

Page 28: ...nt room temperature is displayed permanently in the information field Restoring the defaults The delivery state of the room sensor can be restored by resetting it to its defaults All information the l...

Page 29: ...nsor to its defaults 1 Press and hold the setting button for 5 seconds The dEL and rEs texts briefly appear in the information field The Code Sun and Occupancy icons appear The learned heating time pr...

Page 30: ...The dEL and rEs texts briefly appear in the information field The Code Sun and Occupancy icons appear 2 Wait 15 minutes and the room sensor switches off automatically In order for the en key room set...

Page 31: ...5 seconds The valve controller acknowledges a successful switch off with a series of tones The valve controller is switched off and the connection to the room sensor is broken Activating the service...

Page 32: ...r 1 Activate the service level and select the ACt function 2 Within 15 seconds briefly press the registration button on the valve controller Item Messages Explanation 03 1 ACt Registering of 1 to 4 va...

Page 33: ...de register all registered valve controllers 1 Activate the service level and select the dEL function 2 Press and hold the setting button for 5 seconds The Code Sun and Occupancy icons appear All reg...

Page 34: ...2 Press and hold the registration button for 5 seconds The dEL and rEs functions appear and the display goes blank The room sensor is switched off reset to the default settings and all registered valv...

Page 35: ...m status wireless connection malfunctions 02 Battery Energy storage unit system status 03 Windows Rapid temperature drop detected 04 Prog Valve controllers can be registered 05 Sun Solar cell is activ...

Page 36: ...terrupted 1 hour No valve controllers are being received Antenna Code 2 On On Wireless radio connection partly interrupted 4 hours At least one valve controller is being received Antenna Code 2 Off On...

Page 37: ...the valve controller S 14 System time The room sensor continuously monitors system time If a time or date malfunction is detected in the room sensor Code 3 appears 1 Reset the time and date Code 3 dis...

Page 38: ...regarding the en key room set please contact an authorized service technician directly Caution Housing with a sensitive surface Sponges and abrasive cleaning materials lead to scratches and a dulling...

Page 39: ...39 44 Other en key Technical data 10 5 9 2 19 7 7 0 R 30 0 91 6 90 0 4 1 153 7 2 5 85 5 90 5 46 5 37 5 12 5 M30x1 5 DIN 13 61 8 104 0...

Page 40: ...less protocol 10 mW Communication cycle 10 minutes Connection Service connection None Protection IP30 protection class III IP30 protection class III Ambient conditions operation 0 C 50 C ambient tempe...

Page 41: ...41 44 Other en key...

Page 42: ...en key Other 42 44...

Page 43: ......

Page 44: ...ing is Fun See www enkey de for more information 1 10 60 030 20 2016 02 22 Kieback Peter GmbH Co KG Tempelhofer Weg 50 12347 Berlin Telefon 030 600 95 0 Telefax 030 600 95 164 info enkey de www enkey...

Reviews: