Page 3 of 17    Revision 1.1    Aug 2020

Document No. AlarmLine II Digital EN Controller Installation Instructions 

Important Guidelines

Please read this instruction leaflet thoroughly before commencing installation.

 

Install the AlarmLine II Digital EN Controller accordingly to meet local and country  
installation requirements.

 

The AlarmLine II Digital EN Controller must be installed in accordance with BS 5839-1:2017 (or 
country equivalent) and IEC 60364 and authorities having jurisdiction.

 

Ensure the product is installed, commissioned and maintained by qualified professionals 
according to good engineering practices and who have received sufficient training on  
the unit.

 

Only use Kidde AlarmLine II Digital EN Linear Heat Detection cable with the  
AlarmLine II Digital EN Controller. 

 

Test the Digital Linear Heat Detection cable before connecting it to the AlarmLine II Digital EN 
Controller using a multimeter.

 

Ensure the end of line resistor (3.6kohm) is securely connected at the end each linear heat 
detection cable.

 

If only one zone is required leave the end of line resistor (3.6kohm) connected across the 
terminals of the unused zone.

 

Ensure any cable glands used are tightened to form a secure and moisture proof seal around  
the detection cable and any other cable in or out of the unit.

  Do not exceed the maximum operating voltage of the AlarmLine II Digital EN Controller (36Vdc).

  Do not connect lengths of linear heat detection cable in ‘T’ connections or spurs.

Summary of Contents for Alarmline II Digital EN

Page 1: ...2020 DocumentNo AlarmLineIIDigitalENControllerInstallationInstructions Page 1 of 17 Revision 1 1 Aug 2020 DocumentNo AlarmLineIIDigitalENControllerInstallationInstructions AlarmlineIIDigitalENControl...

Page 2: ...tallation Page 6 Overview Connections Diagram Operating Modes Page 7 Wiring Diagram Independent Wiring Diagram Interlock Useful Information Page 9 Leader Cable Mounting Dimensions Static Discharge Cau...

Page 3: ...d sufficient training on the unit Only use Kidde AlarmLine II Digital EN Linear Heat Detection cable with the AlarmLine II Digital EN Controller Test the Digital Linear Heat Detection cable before con...

Page 4: ...The two zones can operate independently of each other or in interlock mode and a separate alarm and normally conducting fault output are provided for each zone The unit is intended to be installed bet...

Page 5: ...c 36Vdc Current Consumption Normal Operation standby 15mA 7mA 5mA Alarm 40mA 23mA 15mA Operating Temperature Range 20 C 50 C 4 F 122 F Terminal Blocks Spacing 5mm Rising Clamp Rating 16A Wire Size 0 0...

Page 6: ...The fault outputs also stop conducting on power loss to the unit or microprocessor fault triggering a fault at the fire alarm control panel The two wire RS 485 Modbus RTU ASCII output also outputs th...

Page 7: ...erature Digital LHD cables Zone 1 250m Zone 2 120m Power supply 250m 120m NC NO C NC NO C Zone Switch IO Module Zone Switch IO Module Addressable loop Addressable loop RS 485 Modbus RTU A A EOL EOL Ju...

Page 8: ...tion cables must be installed in each protected space See the AlarmLine II Digital EN LHD Installation Instructions for the linear spacing specification Zone 1 250m Zone 2 250m Power supply 250m NC NO...

Page 9: ...vice The mounting holes are located adjacent to the lid screw positions Suitable screws for the type of wall the AlarmLine II Digital EN Controller is to be mounted on will need to be provided for sep...

Page 10: ...s activate only when both Digital LHD zones trigger an alarm 6 Select the relevant operating programme for Zone 1 based on the table below 7 Select the relevant operating programme for Zone 2 based on...

Page 11: ...start of the LHD cable 11 If the Linear Heat Detection cable is connected directly to the AlarmLine II Digital EN Controller then select No and press the Set button to continue 12 Select whether you...

Page 12: ...whenAlarmLineIIDigitalENControllerisinnormaloperation Independentmode Interlockmode NormalOperation 20 Once the unit has been commissioned the display will show the zone status In normal operation th...

Page 13: ...is in fault 24 The unit monitors for interference faults when the input may be changing between alarm ok and fault conditions for example too rapidly In this case an I F fault is displayed on the corr...

Page 14: ...show ok The alarm relays will be o and the fault output normally conducting on 3 In self test mode and alarm condition the display will show alarm The alarm relays will be on After approx 8 seconds th...

Page 15: ...ll respond in the following manner Number of bytes of register values to be read 8 bit Register values 16 bits per register The AlarmLine II Digital EN Controller stores the information for each zone...

Page 16: ...10 seconds continuously While the SET and SELECT buttons are held down the power LED will flash quickly to confirm this procedure is about to take place After approximately 10 seconds the unit will r...

Page 17: ...al state regardless of the state of the other zone Interlock mode The mode on the AlarmLine II Digital EN Controller where the alarm relay outputs will only activate when both Digital LHD cables go in...

Reviews: