Page 16 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Resetting the AlarmLine II Digital EN Controller
WARNING: This procedure will erase ALL stored settings and reset the Kidde AlarmLine II Digital
EN Controller back to its factory default state. The cable types, leader cable calibration, latching
output selection and Modbus setup will all require selecting after this procedure.
To reset the AlarmLine II Digital EN Controller back to the factory state, when the unit is powered up and in
normal operation (see step 20 in the Commissioning procedure), press and hold the SET and SELECT buttons
for a minimum of 10 seconds continuously. While the SET and SELECT buttons are held down the power LED
will flash quickly to confirm this procedure is about to take place. After approximately 10 seconds, the unit
will restart and return to step 1 in the Commissioning procedure. The settings are only erased if the menu
option “New Configs” is selected.