![background image](http://html1.mh-extra.com/html/kidde/alarmline-ii-digital-en/alarmline-ii-digital-en_installation-instructions-manual_1965141010.webp)
Page 10 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
1. After wiring the unit up (see wiring diagram) power up the device.
Device will show screen including software revision number.
2. If the unit is being setup for the first time the following options will
be shown. If the unit has previously been installed the display will
automatically cycle through the options, showing the stored settings.
3. After the initial title screen the next screen will show a menu (see
right) with three options: Load Configs, New Configs and Self Test. On a
previously configured device, after 10s of no button press the device will
automatically proceed to loading saved configs.
4. If “Load Configs” is selected or no button has been pressed after 10s
on a
previously configured device
, the screen will show “Loading Saved
Configs”. The previously saved parameters will then be displayed.
5. Select the operating mode. (see “Operating modes” (pages 7-8)
for more detail.
Independent:
the two zones operate independently of each
other (default).
Interlock:
Both fault outputs activate when a fault occurs on either zone
1 or zone 2. Both alarm outputs activate
only
when both Digital LHD
zones trigger an alarm.
6. Select the relevant operating programme for Zone 1 based on the
table below:
7. Select the relevant operating programme for Zone 2 based on the table
below:
8. If leader cable is connected between the Digital LHD cable and the
AlarmLine II Digital EN Controller and/or the LHD cable is installed in a
hazardous area and IS barriers are being used, the voltage drop to the
start of the LHD cable must be measured by the AlarmLine II Digital EN
Controller in order to ensure correct operation and accurate distance
location. In order to do this, with the leader cable and/or IS barriers and
LHD cable connected to the AlarmLine II Digital EN Controller, short out
the connection at the
start
of the LHD cable. Select “Yes” and press Set to
continue.
Commissioning
MAIN MENU
LOAD CONFIGS
LOADING SAVED
CONFIGS...
Z1 Cable Type:
T078-V10-A045
Z2 Cable Type:
T078-V10-A045
Operating Mode:
INDEPENDENT
Alarm (or activation)
temperature
Cable Set-Up
T078-V10-A045
T088-V10-A065
78°C (EN78)
3
88°C (EN88)
3
Alarm (or activation)
temperature
Cable Set-Up
T078-V10-A045
T088-V10-A065
78°C (EN78)
3
88°C (EN88)
3
In this example, the first option has been chosen
for an alarm temperature of 78°C
In this example, the first option has been chosen
for an alarm temperature of 78°C
Zone 1 ldr cable
Yes
KIDDE ADELCU-2
SW REV 1.6