Page 14 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Testing & Verifi cation
1. If self test mode is selected the device will fi rst load the saved confi gs
then proceed to cycle through normal operation, alarm and fault.
This is to allow the installer/maintenance engineer verify that the unit
is connected to an external system correctly. The screen will fl ash “SELF
TEST/MODE” every few seconds.
2. In self test mode the device cycles between normal operation, alarm
and fault every approx. 8 seconds. In normal operation the display will
show ok. The alarm relays will be off and the fault output normally
conducting (on).
3. In self test mode and alarm condition the display will show alarm.
The alarm relays will be on. After approx. 8 seconds the unit will go into
fault condition.
4. In self test mode and fault condition the display will show fault.
The fault outputs will stop conducting (off ). After approx. 8 seconds the
unit will return to normal condition. To exit self test mode, press and hold
both SET and SELECT buttons for 10s or more until the device resets.
Zone 1: OK
Zone 2: OK
{Zone 1: OK
{Zone 2: OK
Zone 1: ALM
Zone 2: ALM
{Zone 1: ALM
{Zone 2: ALM
Zone 1: FAULT
Zone 2: FAULT
{Zone 1: FAULT
{Zone 2: FAULT
SELF TEST
MODE
LED Illustration
Independent mode
Independent mode
Independent mode
Interlock mode
Interlock mode
Interlock mode